Check
SiUS091601EA
183
Part 6 Service Diagnosis
Check No.02
FTX18/24UVJU, FVXS Series
1. Check the connection of connector.
2. Check motor power supply voltage output (pins 4 - 7).
3. Check motor control voltage (pins 4 - 3).
4. Check rotation command voltage output (pins 4 - 2).
5. Check rotation pulse input (pins 4 - 1).
R6000681
FDMQ Series
1. Turn the power supply OFF.
2. With the fan motor connector disconnected, measure the resistance between each pin, then
make sure that the resistance is more than the value mentioned in the following table.
Measuring points
Judgement
White - Blue
1 MΩ or more
Orange - Blue
100 kΩ or more
Brown - Blue
100 Ω or more
Red - Blue
100 kΩ or more
7
6
5
4
3
2
1
S1
Motor power supply voltage (310 ~ 340 VDC)
Unused
Unused
GND
Motor control voltage (15 VDC)
Rotation command voltage (1~ 6.5 VDC)
Rotation pulse input
White
Orange
Brown
Blue
—
—
Red
FG
Vsp
Vcc
GND
—
—
Vdc/Vm
X8A
(R25080)