SiUS091601EA
Field Settings for FDMQ Series
Part 7 Trial Operation and Field Settings
214
18/24 class
5.3 MAIN/SUB and Address Setting for Wireless Remote
Controller
Outline
If setting multiple wireless remote controllers to operate in one room, perform address setting
for the receiver and the wireless remote controller.
If using both a wired remote controller and a wireless remote controller with 1 indoor unit,
change the MAIN/SUB switch of the signal receiver PCB.
Signal Receiver
PCB Setting
MAIN/SUB switch
Set the MAIN/SUB setting switch (SS1) on the signal receiver PCB to SUB.
Mode
No.
First
Code
No.
Second Code No.
External static pressure
13
(23)
6
05
50 Pa
06
60 Pa
07
70 Pa
08
80 Pa
09
90 Pa
10
100 Pa
11
110 Pa
12
120 Pa
13
130 Pa
14
140 Pa
15
150 Pa
Factory Setting
MAIN
SUB
MAIN/SUB setting
switch (SS1)
R7000181
R7000182
Setting the receiver
(lt is factory set to “1”)
Address setting switch (SS2)
MAIN/SUB setting switch (SS1)
(R24951)
M
S
M
S