SiUS091601EA
Functions for FTX, FVXS Series
Part 4 Functions and Control
52
2.5 Automatic Cooling/Heating Changeover
Outline
When the automatic operation is selected with the remote controller, the microcomputer
automatically determines the operation mode as cooling or heating according to the room
temperature and the set temperature at start-up.
The unit automatically switches the operation mode to maintain the room temperature at the set
temperature.
Details
Ts: set temperature (set by remote controller)
Tt: target temperature (determined by microcomputer)
Tr: room thermistor temperature (detected by room temperature thermistor)
C: correction value
1. The set temperature (Ts) determines the target temperature (Tt).
(Ts = 18 ~ 30°C (64.4 ~ 86°F))
2. The target temperature (Tt) is calculated as;
Tt = Ts + C
where C is the correction value.
C = 0°C (0°F)
3. Thermostat ON/OFF point and operation mode switching point are as follows.
(1) Heating
Cooling switching point:
Tr
Tt + 3.0°C (+ 5.4°F)
(2) Cooling
Heating switching point:
Tr < Tt – 3.0°C (– 5.4°F) (FTX09/12/15NMVJU)
Tr < Tt – 2.5°C (– 4.5°F) (FTX18/24UVJU)
(3) Thermostat ON/OFF point is the same as the ON/OFF point of cooling or heating operation.
4. During initial operation
Tr
Ts : Cooling operation
Tr < Ts : Heating operation
FTX09/12/15NMVJU, FVXS Series
Ex: When the target temperature is 25°C (77°F)
Cooling → 23°C (73.4°F): Thermostat OFF → 22°C (71.6°F): Switch to heating
Heating → 27°C (80.6°F): Thermostat OFF → 28°C (82.4°F): Switch to cooling
FTX18/24UVJU
Ex: When the target temperature is 25°C (77°F)
Cooling → 23°C (73.4°F): Thermostat OFF → 22.5°C (72.5°F): Switch to heating
Heating → 27°C (80.6°F): Thermostat OFF → 28°C (82.4°F): Switch to cooling
Target tempe 3.0°C (+5.4°F)
Heating Operation
Target temperature – 3.0°C (–5.4°F)
Cooling Operation
(R21862)
Target temperature – 2.0°C (–3.6°F)
= Thermostat OFF
Target tempe 2.0°C (+3.6°F)
= Thermostat OFF
Target tempe 3.0°C (+5.4°F)
Heating Operation
Target temperature – 2.5°C (–4.5°F)
Cooling Operation
(R16965)
Target temperature – 2.0°C (–3.6°F)
= Thermostat OFF
Target tempe 2.0°C (+3.6°F)
= Thermostat OFF
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...