Troubleshooting for FTX, FVXS Series
SiUS091601EA
129
Part 6 Service Diagnosis
Note(s)
Reference
Rubber cushion
The rotation pulse is the feedback signal from the indoor fan motor.
Check No.03
09/12 class
15 class
R6000673
R6000674
Check No. 03
Check No. 03
Check No. 03
NO
YES
YES
YES
NO
NO
YES
NO
Is the rotation pulse
generated?
Turn the power on again.
Check the fan motor for
breakdown or short circuit.
Check the motor control voltage.
Check the indoor unit PCB for
rotation pulse.
Fan rotates smoothly?
Resistance OK?
Is the motor control
voltage 15 VDC
generated?
Replace the indoor fan motor.
Replace the indoor unit PCB
(control PCB).
Replace the indoor fan motor.
Replace the indoor unit PCB
(control PCB).
YES
NO
NO
Abnormal
sound occurs?
Is the rubber cushion
properly fitted?
YES
Correct the position of
rubber cushion or replace
the rubber cushion.
Replace the bearing rubber
cushion.
A
Continued from the
previous page
(R24945)
Rubber
cushion
Bearing
rubber
cushion
Rubber
cushion
Bearing
rubber
cushion
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...