SiUS091601EA
Troubleshooting for FTX, FVXS Series
Part 6 Service Diagnosis
132
Reference
5.4 Thermistor or Related Abnormality
Error Code
C4
,
C9
Method of Error
Detection
The temperatures detected by the thermistors determine thermistor errors.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less with
the power on.
Supposed
Causes
Disconnection of connector
Defective thermistor(s)
Defective indoor unit PCB
Troubleshooting
C4
: Indoor heat exchanger thermistor
C9
: Room temperature thermistor
Check No.01
YES
(R21870)
NO
Check No. 01
Check the thermistor resistance
value.
YES
NO
Caution
Correct the connection.
Replace the defective
thermistor(s).
Replace the indoor unit PCB
(control PCB).
Normal?
Normal?
Check the connection of
connectors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.