SiUS091601EA
Field Settings for FDMQ Series
Part 7 Trial Operation and Field Settings
216
Note(s)
Multiple Settings
or
When the indoor unit is controlled by an outside controller (central remote controller, etc.), the
indoor unit sometimes does not respond to ON/OFF command or temperature setting command
from the wireless remote controller. Check what setting the customer needs and make the multiple
setting as shown below.
After Setting
Stick the Unit No. label on the receiver and the back of the wireless remote controller.
Set the Unit No. of the receiver and the wireless remote controller to be the equal. If the settings
differ, the signal from the remote controller cannot be transmitted.
Remote Controller
Indoor Unit
Multiple settings
Remote controller
display
To control other air
conditions and units
For other than on left
: Standard
All items displayed.
Commands other than
ON/OFF and
temperature setting
accepted.
(1 LONG BEEP or 3
SHORT BEEPS
emitted)
All commands
accepted.
(2 SHORT BEEPS)
: Multi System
Operations remain
displayed shortly after
execution
All commands accepted. (2 SHORT BEEPS)
1
Unit No. label (5)
Wireless remote
controller (2)
(R25081)
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...