Part 4 Functions and Control
86
5.10 Defrost Control
Outline
Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat
exchanger temperature must be more than a certain value to finish defrosting.
Details
Conditions for Starting Defrost
The starting conditions are determined with the outdoor temperature and the outdoor heat
exchanger temperature.
The system is in heating operation.
The compressor operates for 6 minutes.
More than
A
minutes (depending on the duration of the previous defrost control) of accumulated
time have passed since the start of the operation, or ending the previous defrosting.
Conditions for Canceling Defrost
The judgment is made with the outdoor heat exchanger temperature (
B
).
09 class
12 class
15 class
18/24 class
A
(minute)
20 ~ 25
20 ~ 25
44
15 ~ 25
B
(°C)
2 ~ 20
2 ~ 20
6 ~ 12
4 ~ 12
(°F)
35.6 ~ 68.0
35.6 ~ 68.0
42.8 ~ 86.0
42.8 ~ 86.0
C
(Hz)
64
40
48
48
D
(Hz)
64
40
70
54
E
(seconds)
40
40
60
60
F
(seconds)
60
60
60
120
G
(seconds)
510
510
340
340
H
(seconds)
50
50
90
60
J
(seconds)
8
8
5
8
K
(pulse)
400
400
450
450
L
(pulse)
300
300
300 ~ 450
400
M
(pulse)
350
350
200
450
Frequency
Compressor
Four way valve
Fan
ON
OFF
ON
OFF
ON
OFF
0 Hz
0 Hz
C
Hz
D
Hz
J
sec.
PI control
8 sec.
H
sec.
(R21661)
E
sec.
F
sec.
G
sec.
L
pulse zone
Electronic
expansion valve
opening
Normal
control
K
pulse
zone
M
pulse
zone
Starting
control
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...