![Daikin FDMQ12RVJU Service Manual Download Page 43](http://html.mh-extra.com/html/daikin/fdmq12rvju/fdmq12rvju_service-manual_501418043.webp)
SiUS091601EA
Outdoor Unit
Part 3 Printed Circuit Board Connector Wiring Diagram
38
Caution
4.3 RXL15QMVJU
Main PCB
Replace the PCB if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
1)
S20
Connector for electronic expansion valve coil
2)
S40
Connector for overload protector
3)
S70
Connector for DC fan motor
4)
S80
Connector for four way valve coil
5)
S90
Connector for thermistors
(outdoor temperature, outdoor heat exchanger, discharge pipe)
6)
HL1, HN1, S
Connector for terminal block
7)
E1, E2
Terminal for ground wire
8)
U, V, W
Connector for compressor
9)
FU1, FU2
Fuse (3.15 A, 250 V)
10)
FU3
Fuse (30 A, 250 V)
11)
J6
Jumper for facility setting
Refer to page 217 for details.
12)
LED A
LED for service monitor (green)
13)
V1, V2, V3
Varistor
U, V, W
FU3
FU1
FU2
V3
V2
V1
S20
S80
S40
S90
J6
S70
2P479271-14
E1, E2
HL1, HN1, S
LED A
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...