Control Specification
SiUS091601EA
81
Part 4 Functions and Control
5.3.3 Four Way Valve Operation Compensation
Outline
At the beginning of operation as the four way valve is switched, the pressure difference to activate
the four way valve is acquired when the output frequency is higher than a certain fixed frequency,
for a certain fixed time.
Details
Starting Conditions
1. When the compressor starts and the four way valve switches from OFF to ON
2. When the four way valve switches from ON to OFF during operation
3. When the compressor starts after resetting
4. When the compressor starts after the fault of four way valve switching
The lower limit of frequency keeps
A
Hz for
B
seconds for any of the conditions above.
When the outdoor temperature is above
C
in heating, the frequency decreases depending on the
outdoor temperature.
5.3.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning off.
The function is not used when defrosting.
5.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
The function is not used when defrosting.
: Values refer to 15/18/24 class only, when outside temperature is lower than –15°C (5°F).
09 class
12 class
15 class
18/24 class
Cooling Heating Cooling Heating Cooling Heating Cooling Heating
A
(Hz)
40
54
24
34
48
46
48
B
(seconds)
60
60
70
60
C
(°C)
10
10
15
15
(°F)
50
50
59
59
09 class
12 class
15 class
15 class
18/24 class
A
(Hz)
40
24
52
35
55/48
B
(Hz)
54
34
68
52
65
C
(Hz)
72
44
80
62
80
D
(Hz)
90
56
98
80
90
E
(Hz)
100
78
—
100
100
F
(seconds)
180
180
300
1300
240
G
(seconds)
420
420
200
250
200
H
(seconds)
180
180
460
300
200
J
(seconds)
120
120
200
200
120
K
(seconds)
400
180
—
120
120
(sec.)
Time
(R23251)
(Hz)
Frequency
C
D
E
B
F
G
H
J
K
A
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...