SiUS091601EA
Trial Operation
Part 7 Trial Operation and Field Settings
204
Wired Remote Controller (BRC1E73)
1. Set to COOL or HEAT operation using the
remote controller.
2. Press and hold
Cancel
button for 4 seconds
or longer. Service settings menu is
displayed.
3. Select
in the service
settings menu, and press
Menu/OK
button.
Basic screen returns and “Test Operation”
is displayed at the bottom.
4. Press
On/Off
button within 10 seconds, and
the test operation starts.
Monitor the operation of the indoor unit for a
minimum of 10 minutes. During test
operation, the indoor unit will continue to
cool/heat regardless of the temperature
setpoint and room temperature.
In the case of above-mentioned
procedures 3 and 4 in reverse order, test
operation can start as well.
5. Press and hold
Cancel
button for 4 seconds
or longer in the basic screen.
Service settings menu is displayed.
6. Select
in the service
settings menu, and press
Menu/OK
button.
Basic screen returns and normal operation
is conducted.
Test operation will stop automatically
after 15 ~ 30 minutes. To stop the
operation, press
On/Off
button.
Test Operation
Test Operation
Basic screen
1.
2.
3.
4.
5.
Service Settings
menu screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Press On/Off button
(within 10 seconds).
6.
Basic screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Cool
Set to
68
F
Wireless Remote Controller (BRC082A43)
1. Press
button and select the COOL or HEAT operation.
2. Press
button twice.
“
TEST
”
is displayed.
3. Press
button within 10 seconds, and the test operation starts.
Monitor the operation of the indoor unit for a minimum of 10 minutes. During test operation,
the indoor unit will continue to cool/heat regardless of the temperature setpoint and room
temperature.
In the case of above-mentioned procedures (1) and (2) in reverse order, test operation
can start as well.
Test operation will stop automatically after 15 ~ 30 minutes.
button.
Some of the functions cannot be used in the test operation mode.
To stop the operation, press
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...