Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis
172
7.12 Thermistor or Related Abnormality (Outdoor Unit)
Error Code
H9
,
J3
,
J6
,
P4
Method of Error
Detection
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less
with the power on.
J3
error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Supposed
Causes
Disconnection of the connector for the thermistor
Defective thermistor(s)
Defective heat exchanger thermistor in the case of
J3
error (outdoor heat exchanger thermistor
in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Troubleshooting
In case of
P4
Replace the outdoor unit PCB (main PCB).
P4
: Radiation fin thermistor
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for FDMQ12RVJU
Page 18: ...SiUS091601EA 13 Part 2 Specifications 1 Specifications 14 Part 2 Specifications ...
Page 198: ...Check SiUS091601EA 193 Part 6 Service Diagnosis 18 24 class R24538 1 2 3 4 Multimeter ...
Page 201: ...SiUS091601EA Check Part 6 Service Diagnosis 196 18 24 class R24539 DC DC W V U ...
Page 229: ...SiUS091601EA Piping Diagrams Part 8 Appendix 224 RXL15QMVJU RXL18UMVJU 3D100007 3D123368 ...
Page 230: ...Piping Diagrams SiUS091601EA 225 Part 8 Appendix RXL24UMVJU 3D107985A ...