12.4.3
[P08: AMIX] Alarm mix output, [P07: WN_M] Warning output level
By changing the parameter `P08: Alarm mix output’ ‘P07: Warning output level’, the digital output DO2 and
contact output function can be selected.
◆
Digital output DO2 and contact output
Parameter
Output signal
P08
Alarm
mix output
P07
Warning
output level
Digital output DO2
Contact output
0
Alarm
ON: Normal
OFF: Alarm
1
Alarm or Warning
ON: Normal
OFF: Alarm
ON
⇔
OFF: Warning
0 or 2
2
Alarm or Warning
ON: Normal
OFF: Alarm or Warning
Pressure switch
0
Alarm or Pressure switch
1
1
2
No output
Alarm or Pressure switch or Warning
12.5
Pressure switch setting
By the pressure switch function, the digital signal detecting the pressure decrease can be output.
By this function, the external pressure switch is not required. So, the system can be formed at low cost.
Please refer to "12.4.1 Parameters" for the method of setting the pressure switch output signal.
12.5.1
Parameters list
No.
Sign
Parameter Name
Range
Factory Default
Setting
Unit
0
~
35.0
(
0: Function disabled
)
0.0
MPa
0
~
507
(
0: Function disabled
)
0.0
×10PSI
P01
SW_L
Pressure switch operating
level
0
~
350
(
0: Function disabled
)
0.0
%
P02
T_SW
Pressure switch output delay
time
0.00
~
9.99
0.00
sec
P03
PSWH
Pressure switch display
holding setting
0: Invalid
1: Display hold
2: Display and record
0
-
P08
AMIX Alarm output mix
0: Individual output
1: Integrated output
2: Pressure switch function
expansion
1
-
0.00
~
1.00
0.50
MPa
P38
P_DF
Pressure switch output dead
zone
0
~
145
72
PSI