PIM00411
9-2
9.1
Wiring diagram
9.2
Installation of breaker
To prevent electrical accidents, please be sure to connect the no-fuse breaker that conforms to EN60947-2 to the
power supply line. Breaker capacity is shown in the following table.
[Breaker setting and rated current]
Power voltage and frequency
Product type
3
φ
200V50Hz
3
φ
200V60Hz
3
φ
220V60Hz
Breaker
setting value
EHU15R-M0701-30 / EHU15R-M0702-30
11.5 A
11.3 A
10.6 A
15A
EHU30R-M0701-30 / EHU30R-M0702-30
15.4.A
15.1 A
13.8 A
20A
9.3
Connecting the main power supply cable
1
)
Please prepare power line, crimp terminal and cable clamp.
Recommended Products
Product Type
Cable Size
Recommended Cable
Recommended
Crimp
Terminals
Recommended Cable Clamp
CE
2.5mm
2
or
more
CE362
2.5mm
2
×4
Core
(
Manufactured by KURAMO
ELECTRIC
)
RBC2-4
Manufactured by OHM
ELECTRIC
OA-W2213
Applicable Cable shape :
Φ
9
~
Φ
13
VCT
3.5mm
2
or
more
VCT360
3.5mm
2
×4
Core
(
Manufactured by KURAMO
ELECTRIC
)
RBC5.5-4
Manufactured by OHM
ELECTRIC
OA-W2216
Applicable Cable shape :
Φ
11
~
Φ
16
2
)
Connect the main power cable through the wiring hole of controller. Please use cable clamp to the wiring
port for meeting the IP54 protection degree.
:
It is located in the "main power supply terminal" of the controller. Please be sure to wire
L1
L2
3φ AC200~220V 50/60Hz
Main circuit
power supply
L3
DI1
DI2
DI3
DI5
ICOM
or
External power
supply(DC+24V)
Negative
common
Positive
common
・
・
・
・
・
Digital input
・
・
・
・
・
:
It is located in the "signal line terminal" of the controller. Please wire
if necessary.
Digital output
DO1
DO2
OCOM
External power
supply(DC+24V)
Negative
common
AL_C
AL_B
or
Positive
common
AL_A