Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
62
4-12 Setting outdoor unit
Set the type of the outdoor unit registered as a Mgmt. point.
1. Log into SE Mode from the Menu List screen and display the Service Settings tab (see page 7).
Touch the Outdoor Setup button on the Service Settings tab to display the Outdoor Setup screen
(see page 10).
(1)
2. Select the desired outdoor unit from the list and touch the
(1)
Type
button.
When the input dialogue is displayed, input the type. The type depends on the model of the
outdoor unit. Check the type in the table on page 63 before setting.
If the specified type of outdoor unit is wrong, leakage check operation cannot be executed
correctly. Be careful when setting the type.
CAUTION
When you use the outdoor unit as Internal Pi, check that the pulse amount is correct in the
detailed information screen.
NOTE