Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
39
3.
Enable/Disable dry operation mode in
Dry Operation Mode
(2)
. When enabled, allows you to
set Dry mode from the touch panel, or the Schedule or Interlocking function. Touch the OK
button to commit and close the screen.
4-3 DIII-NET Engineering
Sets up the iTM as “Main” or “Sub” when also installing an upper central controller. Sets Setpoint
Restriction to “Enable” or “Auto” when also installing an upper central controller (such as: Interface
for use in BACnet, Interface for use in LONWORKS).
1. Log into SE Mode from the Menu List screen and display the Service Settings tab (see page 7).
Touch the DIII-NET Engineering button on the Service Settings tab to display the DIII-NET
Engineering screen (see page 10).
(1)
(2)
(3)
(4)
(5)
2. Set “Main” or “Sub” using the
Main/Sub controller Settings
radio button
(1)
. A restart is
necessary after switching the Main/Sub controller Settings.
When “Sub” is selected,
Setpoint Range Limit if another controller exists
(2)
is greyed out
and cannot be selected. The setting is “always disabled”.
NOTE
3. If you have set “Main” in step 2, select “Enable” or “Auto” in
Setpoint Range Limit if another
controller exists
(2)
.
Enable: The Setpoint Restriction is enabled.
Auto: The Setpoint Restriction is disabled when an upper central unit is present. The Setpoint
Restriction is enabled when an upper central unit is not present.