Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
31
Acceptable range for each numeric value
Detailed
Type
Classification Item
For Celsius
For Fahrenheit
For analog value
Minimum/
Maximum value
(Default value)
Increment
Minimum/
Maximum value
(Default value)
Increment
Minimum/
Maximum value
(Default value)
Increment
External Ai
BACnet Ai
Upper/
Lower
Limit
monitoring
Hysteresis
0.0 to 512.0
(0.0)
0.1
0 to 922
(0)
1
0.00 to
9999.99
(0.00)
0.01
Lower
limit
−512.0 to 512.0
(0.0)
0.1
−890 to 954
(32)
1
−9999.99 to
9999.99
(0.00)
0.01
Upper
limit
−512.0 to 512.0
(0.0)
0.1
−890 to 954
(32)
1
−9999.99 to
9999.99
(0.00)
0.01
Analog
value
Minimum
value
−512.0 to 512.0
(0.0/−512.0)
*
3
0.1
−890 to 954
(32/−890)
*
3
1
−9999.99 to
9999.99
(0.00)
0.01
Maximum
value
−512.0 to 512.0
(100.0/512.0)
*
3
0.1
−890 to 954
(212/954)
*
3
1
−9999.99 to
9999.99
(100.00)
0.01
Internal Ai
Upper/
Lower
Limit
monitoring
Hysteresis
0.0 to 512.0
(0.0)*
2
0.1
0 to 922
(0)*
2
1
Lower
limit
−512.0 to 512.0
(0.0)*
2
0.1
−890 to 954
(32)*
2
1
Upper
limit
−512.0 to 512.0
(0.0)*
2
0.1
−890 to 954
(32)*
2
1
BACnet Ao
Analog
value
Min.
of op
−512.0 to 512.0
(0.0)
0.1
−890 to 954
(32)
1
−9999.99 to
9999.99
(0.00)*
1
0.01*
1
Max.
of op
−512.0 to 512.0
(0.0)
0.1
−890 to 954
(32)
1
−9999.99 to
9999.99
(0.00)*
1
0.01*
1
Displayed
accuracy
−1
(−1)
1
0
(0)
1
−2 to 3
(−1)
1
*1 Min of op. and Max of op. can be set up with the accuracy specified in Displayed accuracy.
If Displayed accuracy is modified when Min of op. and Max of op. are already set, their value are rounded to fit the
accuracy specified by the Displayed accuracy.
(When loading a CSV file, an input data error will occur if it contains any value finer than the specified accuracy.)
*2 The default values displayed on GUI will change depending on whether Celsius or Fahrenheit is selected in System
Settings.
*3 The former or latter value will be used depending on whether Unit Type is Other or Thermistor, respectively.
(When loading a CSV file with Thermistor selected, the default value will be used regardless of the input data.)