Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
80
•
Inform the user that all units are forced to operate in the cooling mode during leakage check.
•
Caution the user not to change the time setting of iTM during leakage check.
•
Power consumed by the indoor unit during leakage check is also proportionally distributed.
•
Leakage check and power limit control (*) cannot be conducted at the same time.
(i) If power limit control is set to [Demand 3(Forced thermo OFF)], it will be conducted before
leakage control.
(ii) If power limit control is set to [Demand 1,Demand 2], leakage check will be conducted first.
* In power limit control, a command is sent to the outdoor unit via the outdoor unit external
control adapter (DTA104A * * ).
•
Leakage check and iTM energy saving control cannot be conducted at the same time.
Leakage check will be conducted before energy saving control.
NOTE