Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
79
Conflict with other controls
The following describes the operation when another control comes into conflict with the Leakage
Check.
: Enabled ×: Disabled
Target
management
point
Other control
Leakage
Check
Mgmt. point
status/Other
control
Remarks
Outdoor
unit
Communication
status
Communication
error
×
If the outdoor unit experiences
communication error within 180
minutes of starting Leakage
Check, “Leakage Check failure” is
recorded in the history.
System
Under
Maintenance
×
Settings modifications from the
Maintenance Setup screen is not
allowed during Leakage Check.
Indoor
unit
*
Central
Monitoring
operation
Stop
×
Central Monitoring operations are
not carried out during Leakage
Check since indoor units are under
maintenance.
Start
×
Equipment error
×
Communication
error
×
Automatic
Control
Schedule Control
×
Automatic Control is disabled
during Leakage Check since
indoor units are under
maintenance.
Interlocking Control
×
Emergency
Stop Control
×
Emergency Stop instructions are
sent also to indoor units under
Leakage Check.
Auto Changeover
×
Automatic Control is disabled
during Leakage Check since
indoor units are under
maintenance.
Temperature
Limit
×
Sliding Temperature
×
HMO
×
Timer Extension
×
Setback
×
Data
collection
Power Proportional
Distribution
Indoor units become under
maintenance during Leakage
Check (however, data can be
collected even under
maintenance)
Energy
Navigator
×
Indoor units become under
maintenance during Leakage
Check (data collection is not
performed during maintenance).
System
Under
Maintenance
×
Settings modifications from the
Maintenance Setup screen is not
allowed during Leakage Check.
* Refers to indoor units registered in the same refrigeration system as the target outdoor unit. In this table,
Enabled/Disabled applies if at least one indoor unit among those registered is in the relevant status.