background image

18

3.  INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT

Example:

 Natural gas with a heating value of 1000 BTU per cubic 

foot and 34 seconds per cubic foot as determined by Step 2, then: 

  Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. 

NOTE: 

BTU content of the gas should be obtained from the gas 

supplier. This measured input must not be greater than 

shown on the unit rating plate.

Adjust input rate by varying the adjustment of the gas pressure 

regulator on the gas valve. All adjustments must be made with fur-

nace operating at high fire and at normal operating temperature. A 

manometer should be connected to the gas valve to verify pressure 

is within the specified range (see following figures for manometer 

connections).  Clockwise rotation of the pressure regulator screw 

increases pressure and gas flow rate. Turn screw counterclock-

wise to decrease pressure and gas flow rate. After adjustment the 

furnace temperature rise must be within the range specified on 

the unit data plate. 

NOTE: 

Thermal efficiency of the furnace is a 

product efficiency rating determined under continuous operating 

conditions independent of any installed system.

Pressure Regulator

Adjustment 

(Under Cap Screw)

Gas Valve

On/Off

Selector

Switch

INLET

OUTLET

Inlet Pressure

Tap

Outlet Pressure

Tap

WHITE-RODGERS 36G22 - SINGLE STAGE

Inlet

Pressure Boss

Low Fire

Regulator Adjust

Manometer

Manometer

Hose

High Fire Regulator

Adjust

Regulator

Vent

Outlet

Pressure Boss

Open to

Atmosphere

WHITE-RODGERS 36G54 (2-STAGE) CONNECTED TO MANOMETER

PRESSURE ADJUSTMENTS

TO CONNECT MANOMETER TO GAS VALVE:

1.  Back outlet pressure test screw (inlet/outlet pressure boss) 

out one turn (counterclockwise, not more than one turn).

2.  Attach a hose and manometer to the outlet pressure boss 

of the valve.

TO REMOVE MANOMETER FROM GAS VALVE:

1.   Remove manometer hose from outlet pressure boss.
2.  Turn outlet pressure test screw in to seal pressure port 

(clockwise, 7 in-lb. minimum).

3.  Turn on electrical power and gas supply to the system.
4.  Turn on system power and energize valve.
5.  Using a leak detection solution or soap suds, check for 

leaks at pressure boss screw.  Bubbles forming indicate a 

leak.  SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY.

T

O

 

PREVENT

 

UNRELIABLE

 

OPERATION

 

OR

 

EQUIPMENT

 

DAMAGE

THE

 

GAS

 

MANIFOLD

 

PRESSURE

 

MUST

 

BE

 

AS

 

SPECIFIED

 

ON

 

THE

 

UNIT

 

RATING

 

PLATE

. O

NLY

 

MINOR

 

ADJUSTMENTS

 

SHOULD

 

BE

 

MADE

 

BY

 

ADJUSTING

 

THE

 

GAS

 

VALVE

 

PRESSURE

 

REGULATOR

.

CAUTION

6. Relight all other appliances turned off in step 1. Be sure all 

pilot burners are operating.

Main Burner Flame Check 

Flames should be stable, soft and blue (dust may cause orange tips 

but they must not be yellow) and extending directly outward from 

the burner without curling, floating or lifting off.

Temperature Rise Check 

Check the temperature rise through the unit by placing thermome-

ters in supply and return air registers as close to the unit as possible. 

Thermometers must not be able to sample temperature directly 

from the unit heat exchangers, or false readings could be obtained.

1.  All registers must be open; all duct dampers must be in their 

final (fully or partially open) position and the unit operated 

for 15 minutes on HIGH FIRE before taking readings.

2.  The temperature rise must be within the range specified 

on the rating plate.

NOTE:

 Air temperature rise is the temperature difference between 

supply and return air.
With a properly designed system, the proper amount of tempera-

ture rise will normally be obtained when the unit is operated at 

rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it may  

be necessary to change the blower speed. A higher blower speed 

will lower the temperature rise. A slower blower speed will increase 

the temperature rise.

NOTE: 

Blower speed MUST be set to give the correct air temperature 

rise through the unit as marked on the rating plate. 

NORMAL SEQUENCE OF OPERATION - HEATING

This unit has one (RS) Manual Reset Limit Control Switch. Check 

the limit to make sure it has not tripped. The limit may arrive at 

the job site tripped as a result of shipping shock.
If the vent motor comes on, but the unit does not attempt igni-

tion, check if the ALS (Automatic Reset High Limit Control Switch) 

requires resetting.

1.  With electricity and gas turned on, the system switch 

Summary of Contents for DBG Series

Page 1: ...ndex Replacement Parts 2 Safety Instructions 2 General Information 3 Unit Location 4 Clearances 6 Roof Curb Post Installation Checks 6 Roof Top Duct Connections 6 Rigging Details 6 Electrical Wiring 8...

Page 2: ...ATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY WARNING SHEET METAL PARTS SCREWS CLIPS AND SIMILAR...

Page 3: ...National Codes It is the installer s responsibility to install the product in accordance with National Codes and or prevailing local codes and regulations The heating and cooling capacities of the un...

Page 4: ...t in an area where the outdoor air i e combustionairfortheunit willbefrequentlycontaminated by compounds containing chlorine or fluorine Common sources of such compounds include swimming pool chemical...

Page 5: ...ove wooden struts and shipping brace per installation instructions The struts are located in the fork holes and are used to protect the unit from damage while lifting with forks The shipping brace is...

Page 6: ...ance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 75 on the service side of the unit is recommended to facilitate possible blower assembly sha...

Page 7: ...contact with the unit during transport Remove wood strutsmountedbeneathunitbaseframebeforesettingunit on roof curb These struts are intended to protect unit baseframefromforkliftdamage Removalisaccomp...

Page 8: ...HE WIRING PROTECT WIRING FROM SHARP EDGES FOLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES DO NOT ROUTE WIRES THROUGH REMOVABLE ACCESS PANELS CAUTION CONDUIT AND FITTINGS MUST BE WEA...

Page 9: ...AND LOW VOLTAGE BLOCK LOCATIONS R control wiring through grommet control wiring Field for linev oltage Ground Lug Field wiring enters from LOW HIGH 25 TONS MODEL POWER AND LOW VOLTAGE BLOCK LOCATIONS...

Page 10: ...RNING IMPORTANT NOTE This unit is factory set to operate on natural gas at the altitudes shown on the rating plate TO PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH WHEN EITHER USING PROPANE GAS ALO...

Page 11: ...to the gas valve to keep it from turning 6 Install a manual shut off valve in a convenient location within six feet of unit between the meter and the unit 7 Tighten all joints securely 8 The unit must...

Page 12: ...high fire and within 6 7 7 3 inches w c low fire at the manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate which depends on...

Page 13: ...3 8 W C WARNING THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING EQUAL TO OR LESS THAN 1 2 PSIG CAUTION 7 There m...

Page 14: ...Responsibility The installing contractor must be certain that All supply and return air ductwork is in place properly sealed and corresponds with installation instructions All thermostats are mounted...

Page 15: ...or nameplate amps are not exceeded A final check of amp draw should be made upon completion of air balancing of the duct system see Appendix B Set Evaporator Fan Rpm Actual RPM s must be set and verif...

Page 16: ...n device which automatically lights the main burner DO NOT try to light burner by any other method 6 Move the gas control valve switch to the OFF position Do not force 7 Wait five minutes to clear out...

Page 17: ...he dripleg and installing a predrilled cap with a hose fitting With Power And Gas On 2 Put unit into heating cycle and turn on all other gas consuming appliances NATURAL Min 5 0 W C Max 10 0 W C PROPA...

Page 18: ...Using a leak detection solution or soap suds check for leaks at pressure boss screw Bubbles forming indicate a leak SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY TO PREVENT UNRELIABLE OPERATION OR EQUIPM...

Page 19: ...lose manual gas shut off valve external to the unit 6 Replace the heat exchanger door on the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Automatic Reset High...

Page 20: ...igeration Sequence Check With the disconnect switch open remove the field connected ther mostat wire from terminal R on TB1 terminal block Place a jumper across terminals R and G and across R and Y on...

Page 21: ...e maintenance is the best way to avoid unnecessary expense and inconvenience Have this system inspected at regu lar intervals by qualified service personnel at least twice a year Routine maintenance s...

Page 22: ...Y ADJUSTMENT CONTACT A QUALIFIED SERVICER AT ONCE IF AN ABNORMAL FLAME SHOULD DEVELOP WARNING At least once a year prior to or during the heating season make a visual check of the burner flames NOTE T...

Page 23: ...ains on The diagnostic fault code is two flashes Pressure Switch Stuck Closed 3 FLASH CODE A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring If the control enco...

Page 24: ...BHP 0 2 9359 4 92 8991 3 79 8621 3 54 8188 3 27 7826 3 04 0 4 9018 3 18 8632 4 39 8251 3 39 7867 3 15 7363 2 85 6992 2 63 0 6 8279 2 96 7879 3 86 7484 2 99 7085 2 75 0 8 7957 4 82 7513 2 73 7097 3 35...

Page 25: ...6 8250 6 12 7657 5 40 7033 4 74 1 2 8934 7 89 8550 7 25 8175 6 57 7598 5 72 7043 5 04 6394 4 38 1 4 8424 7 49 8071 6 91 7639 6 21 7041 5 38 6318 4 63 1 6 7959 7 21 7609 6 57 7088 5 84 6295 4 97 1 8 74...

Page 26: ...RE DROP SCFM 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 In WG 0 15 0 18 0 22 0 27 0 32 0 37 0 42 0 48 0 55 0 61 0 69 0 76 Airflow Pressure Drop of Downflow Economizer for 15 to 25 To...

Page 27: ...lt Drive 7 50 7 5 DCG1807V 575 3 60 9 0 78 0 9 0 78 0 3 0 33 0 7 Model Number Electrical Rating Compressor Circuit 1 Compressor Circuit 2 Outdoor Fan Motor Indoor Fan Motor Optional Powered Convienien...

Page 28: ...DIMENSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 B C D A Model A B C D 15 Ton 20 Ton 133 1 2 88 7 32 50 9 32 5 5 32 25 Ton 133 1 2 88 7 32 53 9 32 5 5 32 NOTE 15 20 ton models have 3 fans 25 ton...

Page 29: ...29 APPENDIX D WIRING DIAGRAMS...

Page 30: ...ED CB2 L2 T3 L1 T2 L3 T1 HIGH SPEED CB1 L2 T3 L1 T2 L3 T1 OR RD BK GY BL YL YL BL GY BK RD OR L3 T3 L2 CC1 L1 T1 T2 L3 T3 L2 CC2 L1 T1 T2 L3 T3 L2 BC1 L1 T1 T2 L3 T3 L2 BC2 L1 T1 T2 T3 T2 T1 COMP 1 RD...

Page 31: ...S ONLY USE NEC CLASS 2 WIRE 4 3 L1 AND L2 ON IIC CONTROL IS 24V INPUT 0140L03767 A COMPONENT LEGEND T1 TERMINAL BLOCK L1 TB2 2 FROM TERMINAL 3 TO TERMINAL 2 ON THE TRANSFORMER 6 FOR 208V OPERATION MOV...

Page 32: ...L3 T1 HIGH SPEED CB1 L2 T3 L1 T2 L3 T1 OR RD BK GY BL YL YL BL GY BK RD OR L3 T3 L2 CC1 L1 T1 T2 L3 T3 L2 CC2 L1 T1 T2 L3 T3 L2 BC1 L1 T1 T2 L3 T3 L2 BC2 L1 T1 T2 T3 T2 T1 COMP 1 RD YL BK CCH1 T3 T2...

Page 33: ...33 Wiring is subject to change Always refer to the wiring diagram on the unit for the most up to date wiring DBG180 DBG240 460 575 3 60 2 SPEED WIRING DIAGRAMS...

Page 34: ...RE SWITCH MAIN LIMIT OPEN BAD SWITCH STICKING GAS VALVE 3 MIN COMP ANTI CYCLE TIMER L2 L3 L1 L2 L3 L1 IIC DIAGNOSTIC BLINK CODES L1 L2 L3 LINE VOLTAGE YL RD BK PU OR 7 7 SEE ACCESSORY KIT LITERATURE F...

Page 35: ...FOR OPTIONAL CONVENIENCE OUTLET WIRING DIAGRAM POWER DIAGRAM F L P M L P PLM PLF BK RD PU L1 L2 L3 T1 T2 T3 LAC MC YL BK BR BK BR YL T3 T2 T1 BR L1 L2 L3 T1 T2 T3 EM GY BL YL RD BL BK OR RD YL BK OR...

Page 36: ...VOLTAGE TERMINAL BLOCK 4 TERMINALS FOR 24VAC PWR RD BK BR WIRE AND 6 TERMINALS FOR 24VAC COM BL WIRE 4 CONNECTIONS SHOWN ARE FOR 1 STAGE HEAT OPERATION WHEN 2 STAGE OPERATION IS REQUIRED REMOVE WH JU...

Page 37: ...necessary Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges Tighten as needed Verify that the crankcase heaters have been energized for 24 hours 9 2014 Date...

Page 38: ...2 Compressor Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature...

Page 39: ...39 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 40: ...products may mean a change in specifications without notice 2019 CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daiki...

Reviews: