ELECTRICAL ENTRANCE LOCATIONS

Unit is equipped with a Low Voltage Terminal Block and has Single 

Point wiring to the contactor.

Low Voltage Control Wiring

1.  A 24V thermostat must be installed for unit operation. 

It may be purchased with the unit or field -supplied.  

Thermostats may be programmable or electromechanical 

as required.

2.   Locate thermostat or remote sensor in the conditioned 

space where it will sense average temperature. Do not 

locate the device where it may be directly exposed to 

supply  air,  sunlight  or  other  sources  of  heat.  Follow 

installation instructions packaged with the thermostat.

3.  Use  #18  AWG  wire  for  24V  control  wiring  runs  not 

exceeding 75 feet. Use #16 AWG wire for 24V control wiring 

runs not exceeding 125 feet. Use #14 AWG wire for 24V 

control wiring runs not exceeding 200 feet. Low voltage 

wiring may be National Electrical Code (NEC) Class 2 where 

permitted by local codes.

4.  Route thermostat wires from sub-base terminals to the 

unit. Control wiring should enter through the duct panel 

(dimple marks entrance location). Connect thermostat and 

any accessory wiring to low voltage terminal block TB1 in 

the main control box.

NOTE: 

Field-supplied conduit may need to be installed depending 

on unit/curb configuration. Use #18 AWG solid conductor wire 

whenever  connecting thermostat wires to terminals on sub-base. 

DO NOT use larger than #18 AWG wire. A transition to #18 AWG 

wire may be required before entering thermostat sub-base.

NOTE:

 Refer to unit wiring diagrams for thermostat hookups.

GAS SUPPLY PIPING

 

T

O

 

PREVENT

 

PERSONAL

 

INJURY

 

OR

 

DEATH

 

DUE

 

TO

 

IMPROPER

 

INSTALLATION

ADJUSTMENT

ALTERATION

SERVICE

 

OR

 

MAINTENANCE

REFER

 

TO

 

THIS

 

MANUAL

. F

OR

 

ADDITIONAL

 

ASSISTANCE

 

OR

 

INFORMATION

CONSULT

 

A

 

QUALIFIED

 

INSTALLER

SERVICE

 

AGENCY

 

OR

 

THE

 

GAS

 

SUPPLIER

.

WARNING

IMPORTANT NOTE: 

This unit is factory set to operate on natural 

gas at the altitudes shown on the rating plate. 

T

O

 

PREVENT

 

PROPERTY

 

DAMAGE

PERSONAL

 

INJURY

 

OR

 

DEATH

 

WHEN

 

EITHER

 

USING

 

PROPANE

 

GAS

 

ALONE

 

OR

 

AT

 

HIGHER

 

ALTITUDES

OBTAIN

 

AND

 

INSTALL

 

THE

 

PROPER

 

CONVERSION

 

KIT

(

S

). F

AILURE

 

TO

 

DO

 

SO

 

CAN

 

RESULT

 

IN

 

UNSATISFACTORY

 

OPERATION

 

AND

/

OR

 

EQUIPMENT

 

DAMAGE

H

IGH

 

ALTITUDE

 

KITS

 

ARE

 

FOR

 U.S. I

NSTALLATIONS

 

ONLY

 

AND

 

ARE

 

NOT

 

APPROVED

 

FOR

 

USE

 

IN

 C

ANADA

.

WARNING

The rating plate is stamped with the model number, type of gas and 

gas input rating. Make sure the unit is equipped to operate on the 

type of gas available. Conversion to propane (LP) gas is permitted 

with the use of the factory authorized conversion kit (see the unit 

Technical Manual for the appropriate kit). For High Altitude derates, 

refer to the latest edition of the National Fuel Gas Code NFPA 54/

ANSI Z223.1. 

NATURAL

Min.   5.0" W.C., Max. 10.0" W.C.

PROPANE

Min. 11.0" W.C., Max. 14.0" W.C.

INLET GAS PRESSURE

Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table Above.

The minimum supply pressure should not vary from that shown in 

the table above because this could prevent the unit from having 

dependable ignition. In addition, gas input to the burners must not 

exceed the rated input shown on the rating plate. Overfiring of the 

unit could result in premature heat exchanger failure.

Piping

IMPORTANT NOTE: 

To avoid possible unsatisfactory operation 

or equipment damage due to under firing of equipment, do not 

undersize the natural/propane gas piping from the meter/tank to 

the unit. When sizing a trunk line, include all appliances on that 

line that could be operated simultaneously.
The rating plate is stamped with the model number, type of gas 

and gas input rating. Make sure the unit is equipped to operate 

on the type of gas available.  The gas line installation must comply 

with local codes, or in the absence of local codes, with the latest 

edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1. 

Summary of Contents for DBG Series

Page 1: ...ndex Replacement Parts 2 Safety Instructions 2 General Information 3 Unit Location 4 Clearances 6 Roof Curb Post Installation Checks 6 Roof Top Duct Connections 6 Rigging Details 6 Electrical Wiring 8...

Page 2: ...ATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY WARNING SHEET METAL PARTS SCREWS CLIPS AND SIMILAR...

Page 3: ...National Codes It is the installer s responsibility to install the product in accordance with National Codes and or prevailing local codes and regulations The heating and cooling capacities of the un...

Page 4: ...t in an area where the outdoor air i e combustionairfortheunit willbefrequentlycontaminated by compounds containing chlorine or fluorine Common sources of such compounds include swimming pool chemical...

Page 5: ...ove wooden struts and shipping brace per installation instructions The struts are located in the fork holes and are used to protect the unit from damage while lifting with forks The shipping brace is...

Page 6: ...ance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 75 on the service side of the unit is recommended to facilitate possible blower assembly sha...

Page 7: ...contact with the unit during transport Remove wood strutsmountedbeneathunitbaseframebeforesettingunit on roof curb These struts are intended to protect unit baseframefromforkliftdamage Removalisaccomp...

Page 8: ...HE WIRING PROTECT WIRING FROM SHARP EDGES FOLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES DO NOT ROUTE WIRES THROUGH REMOVABLE ACCESS PANELS CAUTION CONDUIT AND FITTINGS MUST BE WEA...

Page 9: ...AND LOW VOLTAGE BLOCK LOCATIONS R control wiring through grommet control wiring Field for linev oltage Ground Lug Field wiring enters from LOW HIGH 25 TONS MODEL POWER AND LOW VOLTAGE BLOCK LOCATIONS...

Page 10: ...RNING IMPORTANT NOTE This unit is factory set to operate on natural gas at the altitudes shown on the rating plate TO PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH WHEN EITHER USING PROPANE GAS ALO...

Page 11: ...to the gas valve to keep it from turning 6 Install a manual shut off valve in a convenient location within six feet of unit between the meter and the unit 7 Tighten all joints securely 8 The unit must...

Page 12: ...high fire and within 6 7 7 3 inches w c low fire at the manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate which depends on...

Page 13: ...3 8 W C WARNING THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING EQUAL TO OR LESS THAN 1 2 PSIG CAUTION 7 There m...

Page 14: ...Responsibility The installing contractor must be certain that All supply and return air ductwork is in place properly sealed and corresponds with installation instructions All thermostats are mounted...

Page 15: ...or nameplate amps are not exceeded A final check of amp draw should be made upon completion of air balancing of the duct system see Appendix B Set Evaporator Fan Rpm Actual RPM s must be set and verif...

Page 16: ...n device which automatically lights the main burner DO NOT try to light burner by any other method 6 Move the gas control valve switch to the OFF position Do not force 7 Wait five minutes to clear out...

Page 17: ...he dripleg and installing a predrilled cap with a hose fitting With Power And Gas On 2 Put unit into heating cycle and turn on all other gas consuming appliances NATURAL Min 5 0 W C Max 10 0 W C PROPA...

Page 18: ...Using a leak detection solution or soap suds check for leaks at pressure boss screw Bubbles forming indicate a leak SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY TO PREVENT UNRELIABLE OPERATION OR EQUIPM...

Page 19: ...lose manual gas shut off valve external to the unit 6 Replace the heat exchanger door on the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Automatic Reset High...

Page 20: ...igeration Sequence Check With the disconnect switch open remove the field connected ther mostat wire from terminal R on TB1 terminal block Place a jumper across terminals R and G and across R and Y on...

Page 21: ...e maintenance is the best way to avoid unnecessary expense and inconvenience Have this system inspected at regu lar intervals by qualified service personnel at least twice a year Routine maintenance s...

Page 22: ...Y ADJUSTMENT CONTACT A QUALIFIED SERVICER AT ONCE IF AN ABNORMAL FLAME SHOULD DEVELOP WARNING At least once a year prior to or during the heating season make a visual check of the burner flames NOTE T...

Page 23: ...ains on The diagnostic fault code is two flashes Pressure Switch Stuck Closed 3 FLASH CODE A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring If the control enco...

Page 24: ...BHP 0 2 9359 4 92 8991 3 79 8621 3 54 8188 3 27 7826 3 04 0 4 9018 3 18 8632 4 39 8251 3 39 7867 3 15 7363 2 85 6992 2 63 0 6 8279 2 96 7879 3 86 7484 2 99 7085 2 75 0 8 7957 4 82 7513 2 73 7097 3 35...

Page 25: ...6 8250 6 12 7657 5 40 7033 4 74 1 2 8934 7 89 8550 7 25 8175 6 57 7598 5 72 7043 5 04 6394 4 38 1 4 8424 7 49 8071 6 91 7639 6 21 7041 5 38 6318 4 63 1 6 7959 7 21 7609 6 57 7088 5 84 6295 4 97 1 8 74...

Page 26: ...RE DROP SCFM 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 In WG 0 15 0 18 0 22 0 27 0 32 0 37 0 42 0 48 0 55 0 61 0 69 0 76 Airflow Pressure Drop of Downflow Economizer for 15 to 25 To...

Page 27: ...lt Drive 7 50 7 5 DCG1807V 575 3 60 9 0 78 0 9 0 78 0 3 0 33 0 7 Model Number Electrical Rating Compressor Circuit 1 Compressor Circuit 2 Outdoor Fan Motor Indoor Fan Motor Optional Powered Convienien...

Page 28: ...DIMENSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 B C D A Model A B C D 15 Ton 20 Ton 133 1 2 88 7 32 50 9 32 5 5 32 25 Ton 133 1 2 88 7 32 53 9 32 5 5 32 NOTE 15 20 ton models have 3 fans 25 ton...

Page 29: ...29 APPENDIX D WIRING DIAGRAMS...

Page 30: ...ED CB2 L2 T3 L1 T2 L3 T1 HIGH SPEED CB1 L2 T3 L1 T2 L3 T1 OR RD BK GY BL YL YL BL GY BK RD OR L3 T3 L2 CC1 L1 T1 T2 L3 T3 L2 CC2 L1 T1 T2 L3 T3 L2 BC1 L1 T1 T2 L3 T3 L2 BC2 L1 T1 T2 T3 T2 T1 COMP 1 RD...

Page 31: ...S ONLY USE NEC CLASS 2 WIRE 4 3 L1 AND L2 ON IIC CONTROL IS 24V INPUT 0140L03767 A COMPONENT LEGEND T1 TERMINAL BLOCK L1 TB2 2 FROM TERMINAL 3 TO TERMINAL 2 ON THE TRANSFORMER 6 FOR 208V OPERATION MOV...

Page 32: ...L3 T1 HIGH SPEED CB1 L2 T3 L1 T2 L3 T1 OR RD BK GY BL YL YL BL GY BK RD OR L3 T3 L2 CC1 L1 T1 T2 L3 T3 L2 CC2 L1 T1 T2 L3 T3 L2 BC1 L1 T1 T2 L3 T3 L2 BC2 L1 T1 T2 T3 T2 T1 COMP 1 RD YL BK CCH1 T3 T2...

Page 33: ...33 Wiring is subject to change Always refer to the wiring diagram on the unit for the most up to date wiring DBG180 DBG240 460 575 3 60 2 SPEED WIRING DIAGRAMS...

Page 34: ...RE SWITCH MAIN LIMIT OPEN BAD SWITCH STICKING GAS VALVE 3 MIN COMP ANTI CYCLE TIMER L2 L3 L1 L2 L3 L1 IIC DIAGNOSTIC BLINK CODES L1 L2 L3 LINE VOLTAGE YL RD BK PU OR 7 7 SEE ACCESSORY KIT LITERATURE F...

Page 35: ...FOR OPTIONAL CONVENIENCE OUTLET WIRING DIAGRAM POWER DIAGRAM F L P M L P PLM PLF BK RD PU L1 L2 L3 T1 T2 T3 LAC MC YL BK BR BK BR YL T3 T2 T1 BR L1 L2 L3 T1 T2 T3 EM GY BL YL RD BL BK OR RD YL BK OR...

Page 36: ...VOLTAGE TERMINAL BLOCK 4 TERMINALS FOR 24VAC PWR RD BK BR WIRE AND 6 TERMINALS FOR 24VAC COM BL WIRE 4 CONNECTIONS SHOWN ARE FOR 1 STAGE HEAT OPERATION WHEN 2 STAGE OPERATION IS REQUIRED REMOVE WH JU...

Page 37: ...necessary Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges Tighten as needed Verify that the crankcase heaters have been energized for 24 hours 9 2014 Date...

Page 38: ...2 Compressor Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature...

Page 39: ...39 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 40: ...products may mean a change in specifications without notice 2019 CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daiki...

Reviews: