background image

14

STARTUP, ADJUSTMENTS, AND CHECKS

HIGH VOLTAGE!

T

O

 

AVOID

 

PERSONAL

 

INJURY

 

OR

 

DEATH

 

DUE

 

TO

 

ELECTRICAL

 

SHOCK

BOND

 

THE

 

FRAME

 

OF

 

THIS

 

UNIT

 

TO

 

THE

 

BUILDING

 

ELECTRICAL

 

GROUND

 

BY

 

USE

 

OF

 

THE

 

GROUNDING

 

TERMINAL

 

PROVIDED

 

OR

 

OTHER

 

ACCEPTABLE

 

MEANS

. D

ISCONNECT

 

ALL

 

POWER

 

BEFORE

 

SERVICING

 

OR

 

INSTALLING

 

THIS

 

UNIT

.

WARNING

Pre-Startup Instructions - General

T

O

 

PREVENT

 

PROPERTY

 

DAMAGE

 

OR

 

PERSONAL

 

INJURY

, D

O

 

NOT

 

START

 

THE

 

UNIT

 

UNTIL

 

ALL

 

NECESSARY

 

PRE

-

CHECKS

 

AND

 

TEST

 

HAVE

 

BEEN

 

PERFORMED

.

CAUTION

Prior to the beginning of Startup, Adjustments, and Checks pro-

cedures, the following steps should be completed in the building.

MOVING MACHINERY HAZARD!

T

O

 

PREVENT

 

POSSIBLE

 

PERSONAL

 

INJURY

 

OR

 

DEATH

DISCONNECT

 

POWER

 

TO

 

THE

 

UNIT

 

AND

 

PADLOCK

 

IN

 

THE

 “OFF” 

POSITION

 

BEFORE

 

SERVICING

 

FANS

.

WARNING

This unit is equipped with an electronic ignition device to auto-

matically light the main burners. It also has a power vent blower 

to exhaust combustion products.
On new installations, or if a major component has been replaced, 

the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If 

any sparking, odors, or unusual sounds are encountered, shut off 

electrical power and recheck for wiring errors, or obstructions in 

or near the blower motors. 

Duct covers must be removed before 

operating unit.

The Startup, Adjustments, and Checks procedure provides a step-

by-step sequence which, if followed, will assure the proper startup 

of the equipment in the minimum amount of time. Air balancing 

of duct system is not considered part of this procedure. However, 

it is an important phase of any air conditioning system startup and 

should be performed upon completion of the Startup, Adjustments, 

and Checks procedure. The Startup, Adjustments, and Checks 

procedure at outside ambients below 55°F should be limited to 

a readiness check of the refrigeration system with the required 

final check and calibration left to be completed when the outside 

ambient rises above 55°F.

Temporary Heating Or Cooling

If the unit is to be used for temporary heating or cooling, a “Startup, 

Adjustments, and Checks” must first be performed in accordance 

with this manual. Damage or repairs due to failure to comply with 

these requirements are not covered under the warranty. 

After 

the 

machines are used for temporary heating or cooling, inspect the 

coils, fans, and motors for unacceptable levels of construction dust 

and dirt and install new filters.

Contractor Responsibility

The installing contractor must be certain that:

•  All supply and return air ductwork is in place, properly 

sealed, and corresponds with installation instructions.

•  All thermostats are mounted and wired in accordance 

with installation instructions.

•  All  electric  power,  all  gas,  hot  water  or  steam  line 

connections, and the condensate drain installation have 

been made to each unit on the job. These main supply 

lines must be functional and capable of operating all units 

simultaneously.

•  Requirements are met for venting and combution air.
•  Air filters are in place.
•  Input rate and temperature rise are adjusted per rating 

plate.

Roof Curb Installation Check

Inspect the roof curb for correct installation. The unit and curb 

assembly should be level. Inspect the flashing of the roof mounting 

curb to the roof, especially at the corners, for good workmanship. 

Also check for leaks around gaskets. Note any deficiencies in a 

separate report and forward to the contractor. 

Obstructions, Fan Clearance and Wiring

Remove any extraneous construction and shipping materials that 

may be found during this procedure.  Rotate all fans manually to 

check for proper clearances and that they rotate freely. Check for 

bolts and screws that may have jarred loose during shipment to the 

job site. Retighten if necessary. Re-tighten all electrical connections.

Field Duct Connections

Verify that all duct connections are tight and that there is no air 

bypass between supply and return.

Filter Section Check

Remove filter section access panels and check that filters are prop-

erly installed. Note airflow arrows on filter frames.

Pre-startup Precautions

It is important to your safety that the unit has been properly 

grounded during installation. Check  ground lug connection in main 

control box for tightness prior to closing circuit breaker or discon-

nect switch. Verify that supply voltage on line side of disconnect 

agrees with voltage on unit identification plate and is within the  

utilization voltage range as indicated in Appendix C Electrical Data.

System Voltage - 

That nominal voltage value assigned to a circuit 

or system for the purpose of designating its voltage class.

Nameplate Voltage - 

That voltage assigned to a piece of equip-

ment for the purpose of designating its voltage class and for the 

purpose of defining the minimum and maximum voltage at which 

the equipment will operate. 

Utilization Voltage - 

The voltage of the line terminals of the equip-

ment at which the equipment must give fully satisfactory perfor-

mance. Once it is established that supply voltage will be maintained 

within the utilization range under all system conditions, check 

Summary of Contents for DBG Series

Page 1: ...ndex Replacement Parts 2 Safety Instructions 2 General Information 3 Unit Location 4 Clearances 6 Roof Curb Post Installation Checks 6 Roof Top Duct Connections 6 Rigging Details 6 Electrical Wiring 8...

Page 2: ...ATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY WARNING SHEET METAL PARTS SCREWS CLIPS AND SIMILAR...

Page 3: ...National Codes It is the installer s responsibility to install the product in accordance with National Codes and or prevailing local codes and regulations The heating and cooling capacities of the un...

Page 4: ...t in an area where the outdoor air i e combustionairfortheunit willbefrequentlycontaminated by compounds containing chlorine or fluorine Common sources of such compounds include swimming pool chemical...

Page 5: ...ove wooden struts and shipping brace per installation instructions The struts are located in the fork holes and are used to protect the unit from damage while lifting with forks The shipping brace is...

Page 6: ...ance around the unit should be kept for safety service maintenance and proper unit operation A clearance of 75 on the service side of the unit is recommended to facilitate possible blower assembly sha...

Page 7: ...contact with the unit during transport Remove wood strutsmountedbeneathunitbaseframebeforesettingunit on roof curb These struts are intended to protect unit baseframefromforkliftdamage Removalisaccomp...

Page 8: ...HE WIRING PROTECT WIRING FROM SHARP EDGES FOLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES DO NOT ROUTE WIRES THROUGH REMOVABLE ACCESS PANELS CAUTION CONDUIT AND FITTINGS MUST BE WEA...

Page 9: ...AND LOW VOLTAGE BLOCK LOCATIONS R control wiring through grommet control wiring Field for linev oltage Ground Lug Field wiring enters from LOW HIGH 25 TONS MODEL POWER AND LOW VOLTAGE BLOCK LOCATIONS...

Page 10: ...RNING IMPORTANT NOTE This unit is factory set to operate on natural gas at the altitudes shown on the rating plate TO PREVENT PROPERTY DAMAGE PERSONAL INJURY OR DEATH WHEN EITHER USING PROPANE GAS ALO...

Page 11: ...to the gas valve to keep it from turning 6 Install a manual shut off valve in a convenient location within six feet of unit between the meter and the unit 7 Tighten all joints securely 8 The unit must...

Page 12: ...high fire and within 6 7 7 3 inches w c low fire at the manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate which depends on...

Page 13: ...3 8 W C WARNING THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING EQUAL TO OR LESS THAN 1 2 PSIG CAUTION 7 There m...

Page 14: ...Responsibility The installing contractor must be certain that All supply and return air ductwork is in place properly sealed and corresponds with installation instructions All thermostats are mounted...

Page 15: ...or nameplate amps are not exceeded A final check of amp draw should be made upon completion of air balancing of the duct system see Appendix B Set Evaporator Fan Rpm Actual RPM s must be set and verif...

Page 16: ...n device which automatically lights the main burner DO NOT try to light burner by any other method 6 Move the gas control valve switch to the OFF position Do not force 7 Wait five minutes to clear out...

Page 17: ...he dripleg and installing a predrilled cap with a hose fitting With Power And Gas On 2 Put unit into heating cycle and turn on all other gas consuming appliances NATURAL Min 5 0 W C Max 10 0 W C PROPA...

Page 18: ...Using a leak detection solution or soap suds check for leaks at pressure boss screw Bubbles forming indicate a leak SHUT OFF GAS AND FIX ALL LEAKS IMMEDIATELY TO PREVENT UNRELIABLE OPERATION OR EQUIPM...

Page 19: ...lose manual gas shut off valve external to the unit 6 Replace the heat exchanger door on the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Automatic Reset High...

Page 20: ...igeration Sequence Check With the disconnect switch open remove the field connected ther mostat wire from terminal R on TB1 terminal block Place a jumper across terminals R and G and across R and Y on...

Page 21: ...e maintenance is the best way to avoid unnecessary expense and inconvenience Have this system inspected at regu lar intervals by qualified service personnel at least twice a year Routine maintenance s...

Page 22: ...Y ADJUSTMENT CONTACT A QUALIFIED SERVICER AT ONCE IF AN ABNORMAL FLAME SHOULD DEVELOP WARNING At least once a year prior to or during the heating season make a visual check of the burner flames NOTE T...

Page 23: ...ains on The diagnostic fault code is two flashes Pressure Switch Stuck Closed 3 FLASH CODE A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring If the control enco...

Page 24: ...BHP 0 2 9359 4 92 8991 3 79 8621 3 54 8188 3 27 7826 3 04 0 4 9018 3 18 8632 4 39 8251 3 39 7867 3 15 7363 2 85 6992 2 63 0 6 8279 2 96 7879 3 86 7484 2 99 7085 2 75 0 8 7957 4 82 7513 2 73 7097 3 35...

Page 25: ...6 8250 6 12 7657 5 40 7033 4 74 1 2 8934 7 89 8550 7 25 8175 6 57 7598 5 72 7043 5 04 6394 4 38 1 4 8424 7 49 8071 6 91 7639 6 21 7041 5 38 6318 4 63 1 6 7959 7 21 7609 6 57 7088 5 84 6295 4 97 1 8 74...

Page 26: ...RE DROP SCFM 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 In WG 0 15 0 18 0 22 0 27 0 32 0 37 0 42 0 48 0 55 0 61 0 69 0 76 Airflow Pressure Drop of Downflow Economizer for 15 to 25 To...

Page 27: ...lt Drive 7 50 7 5 DCG1807V 575 3 60 9 0 78 0 9 0 78 0 3 0 33 0 7 Model Number Electrical Rating Compressor Circuit 1 Compressor Circuit 2 Outdoor Fan Motor Indoor Fan Motor Optional Powered Convienien...

Page 28: ...DIMENSIONS VERTICAL DISCHARGE TOP VIEW 21 60 7 48 22 B C D A Model A B C D 15 Ton 20 Ton 133 1 2 88 7 32 50 9 32 5 5 32 25 Ton 133 1 2 88 7 32 53 9 32 5 5 32 NOTE 15 20 ton models have 3 fans 25 ton...

Page 29: ...29 APPENDIX D WIRING DIAGRAMS...

Page 30: ...ED CB2 L2 T3 L1 T2 L3 T1 HIGH SPEED CB1 L2 T3 L1 T2 L3 T1 OR RD BK GY BL YL YL BL GY BK RD OR L3 T3 L2 CC1 L1 T1 T2 L3 T3 L2 CC2 L1 T1 T2 L3 T3 L2 BC1 L1 T1 T2 L3 T3 L2 BC2 L1 T1 T2 T3 T2 T1 COMP 1 RD...

Page 31: ...S ONLY USE NEC CLASS 2 WIRE 4 3 L1 AND L2 ON IIC CONTROL IS 24V INPUT 0140L03767 A COMPONENT LEGEND T1 TERMINAL BLOCK L1 TB2 2 FROM TERMINAL 3 TO TERMINAL 2 ON THE TRANSFORMER 6 FOR 208V OPERATION MOV...

Page 32: ...L3 T1 HIGH SPEED CB1 L2 T3 L1 T2 L3 T1 OR RD BK GY BL YL YL BL GY BK RD OR L3 T3 L2 CC1 L1 T1 T2 L3 T3 L2 CC2 L1 T1 T2 L3 T3 L2 BC1 L1 T1 T2 L3 T3 L2 BC2 L1 T1 T2 T3 T2 T1 COMP 1 RD YL BK CCH1 T3 T2...

Page 33: ...33 Wiring is subject to change Always refer to the wiring diagram on the unit for the most up to date wiring DBG180 DBG240 460 575 3 60 2 SPEED WIRING DIAGRAMS...

Page 34: ...RE SWITCH MAIN LIMIT OPEN BAD SWITCH STICKING GAS VALVE 3 MIN COMP ANTI CYCLE TIMER L2 L3 L1 L2 L3 L1 IIC DIAGNOSTIC BLINK CODES L1 L2 L3 LINE VOLTAGE YL RD BK PU OR 7 7 SEE ACCESSORY KIT LITERATURE F...

Page 35: ...FOR OPTIONAL CONVENIENCE OUTLET WIRING DIAGRAM POWER DIAGRAM F L P M L P PLM PLF BK RD PU L1 L2 L3 T1 T2 T3 LAC MC YL BK BR BK BR YL T3 T2 T1 BR L1 L2 L3 T1 T2 T3 EM GY BL YL RD BL BK OR RD YL BK OR...

Page 36: ...VOLTAGE TERMINAL BLOCK 4 TERMINALS FOR 24VAC PWR RD BK BR WIRE AND 6 TERMINALS FOR 24VAC COM BL WIRE 4 CONNECTIONS SHOWN ARE FOR 1 STAGE HEAT OPERATION WHEN 2 STAGE OPERATION IS REQUIRED REMOVE WH JU...

Page 37: ...necessary Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges Tighten as needed Verify that the crankcase heaters have been energized for 24 hours 9 2014 Date...

Page 38: ...2 Compressor Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature...

Page 39: ...39 THIS PAGE INTENTIONALLY LEFT BLANK...

Page 40: ...products may mean a change in specifications without notice 2019 CUSTOMER FEEDBACK Daikin is very interested in all product comments Please fill out the feedback form on the following link https daiki...

Reviews: