SiUS30-604
Troubleshooting by Indication on the Remote Controller
Troubleshooting
189
2.24
“
J7
”
Malfunction of Liquid Pipe Thermistor (R6T)
Remote
Controller
Display
J7
Applicable
Models
RWEYQ60, 72, 84MTJU
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by receiver outlet liquid pipe
thermistor.
Malfunction
Decision
Conditions
When the liquid pipe thermistor is short circuited or open.
Supposed
Causes
Faulty liquid pipe thermistor (R6T)
Faulty outside unit PC board
Troubleshooting
∗
2: Refer to thermistor resistance / temperature characteristics table on P278.
(V3075)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R6T) from outside unit PC
board normal?
(3.5 k
Ω
to
360 k
Ω
)
Replace outside unit PC board
(A1P).
Connect the connector and operate
unit again.
NO
NO
Replace thermistor (R6T).
YES
YES
Is
the connector
for receiver
outlet liquid pipe thermistor
connected to X37A on
outside unit PC
board (A1P)?
Summary of Contents for BSVQ36MVJU
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Page 13: ...Introduction SiUS30 604 xii ...
Page 27: ...Capacity Range SiUS30 604 14 General Information ...
Page 49: ...Specifications SiUS30 604 36 Specifications ...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Page 309: ...SiUS39 601 iv Index ...