SiUS30-604
Specifications
Specifications
17
Notes:
1.
★
1 Indoor temp. : 80°FDB, 67°FWB / inlet water temp. : 85°F / outlet water temp. : 95°F
Equivalent piping length : 25ft, level difference : 0ft.
★
2 Indoor temp. : 70°FDB, 60°FWB / inlet water temp. : 70°F / Equivalent piping length : 25ft, level difference : 0ft.
★
3 In the case of heat pump system, suction gas pipe is not used.
★
4 In the case of heat recovery system.
★
5 In the case of heat pump system.
2. This unit cannot be installed outdoors.
Install indoors (Machine room etc.).
3. Hold ambient condition at 35~95°F, ~80%RH
Heat rejection from the casing : 0.64kW
4. There are some cases where capacity decreases depending on operating states.
Model Name
RWEYQ72MTJU
★
1 Cooling Capacity
Btu / h
72,000
★
2 Heating Capacity
Btu / h
81,000
Casing Color
Ivory White (5Y7.5/1)
Dimensions: (H×W×D)
in
39-3/8×30-3/4×21-11/16
Heat Exchanger
Stainless Steel Plate Type
Comp.
Type
Hermetically Sealed Scroll Type
Piston Displacement
m³/h
11.18
Number of Revolutions
r.p.m
5,280
Motor Output×Number
of Units
kW
3.6
Starting Method
Soft Start
Connecting
Pipes
Liquid Pipe
in
3/8 in C1220T (Flare Connection)
Suction Gas Pipe
in
3/4 in C1220T (Brazing Connection)
★
3
Discharge Gas Pipe
in
★
4 5/8 in C1220T,
★
5 3/4 in C1220T (Brazing Connection)
Water inlet
1 1/4 FPT Female Thread
Water outlet
1 1/4 FPT Female Thread
Drain outlet
1/2 FPS Female Thread
Machine Weight (Mass)
Lbs
330
Sound Level (Reference Value)
dBA
50
Safety Devices
High Pressure Switch, Inverter Overload Protector, Fusible Plugs
Capacity Control
%
23~100
Refrigerant
Refrigerant Name
R-410A
Charge Lbs
9.9
Control
Electronic Expansion Valve
Refrigerator Oil
Synthetic (Ether) Oil
Standard Accessories
Installation Manual, Operation Manual, Connection Pipes, Clamps, Strainer, Conduit Mounting Plate
Drawing No.
4D054571D
Summary of Contents for BSVQ36MVJU
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Page 13: ...Introduction SiUS30 604 xii ...
Page 27: ...Capacity Range SiUS30 604 14 General Information ...
Page 49: ...Specifications SiUS30 604 36 Specifications ...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Page 309: ...SiUS39 601 iv Index ...