Specifications
SiUS30-604
32
Specifications
Wall Mounted Type
Notes:
★
1 Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25ft (Horizontal)
★
2 Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25ft (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
★
4 Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
Model
FXAQ07MVJU
FXAQ09MVJU
FXAQ12MVJU
★
1 Cooling Capacity
Btu/h
7,500
9,500
12,000
★
2 Heating Capacity
Btu/h
8,500
10,500
13,500
Casing Color
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
White (3.0Y8.5/0.5)
Dimensions: (H×W×D)
in
11–3/8×31–1/4×9
11–3/8×31–1/4×9
11–3/8×31–1/4×9
Coil (Cross
Fin Coil)
Rows×Stages×FPI
2×14×17
2×14×17
2×14×17
Face Area
ft²
1.73
1.73
1.73
Fan
Model
QCL9661M
QCL9661M
QCL9661M
Type
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Motor Output
HP
0.054
0.054
0.054
Air Flow Rate (H/L)
cfm
260/160
280/175
300/180
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Foamed Polystyrene /
Foamed Polyethylene
Air Filter
Resin Net (Washable)
Resin Net (Washable)
Resin Net (Washable)
Piping
Connections
Liquid Pipes
in
φ
1/4 (Flare Connection)
φ
1/4 (Flare Connection)
φ
1/4 (Flare Connection)
Gas Pipes
in
φ
1/2 (Flare Connection)
φ
1/2 (Flare Connection)
φ
1/2 (Flare Connection)
Drain Pipe
in
VP13
(External Dia. 11/16 Internal Dia. 1/2)
VP13
(External Dia. 11/16 Internal Dia. 1/2)
VP13
(External Dia. 11/16 Internal Dia. 1/2)
Machine Weight (Mass)
Lbs
25
25
25
★
4 Sound Level (H)
dBA
36
37
38
Safety Devices
Fuse
Fuse
Fuse
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable outdoor unit
R-410A Series
R-410A Series
R-410A Series
Standard Accessories
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
Operation Manual, Installation Manual,
Installation Panel, Paper Pattern for
Installation, Insulation Tube, Clamps,
Screws.
Drawing No.
C:3D046038A
Summary of Contents for BSVQ36MVJU
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Page 13: ...Introduction SiUS30 604 xii ...
Page 27: ...Capacity Range SiUS30 604 14 General Information ...
Page 49: ...Specifications SiUS30 604 36 Specifications ...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Page 309: ...SiUS39 601 iv Index ...