Troubleshooting by Indication on the Remote Controller
SiUS30-604
194
Troubleshooting
Troubleshooting
∗
1: Voltage measurement point
∗
2: Refer to pressure sensor, pressure / voltage characteristics table on P280.
(V2808)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
The
relationship
between the
∗
1
VH and low pressure is
normal (see
∗
2) when voltage
is measured between X45A pins
(2) and (3) of outside unit
PC board (A1P)
(see
∗
1).
Replace the low pressure sensor.
Connect low pressure sensor
property and restart system.
NO
NO
Replace outside unit PC board
A1P.
YES
YES
The low
pressure sensor is
connected to X45A (blue)
of outside unit PC
board (A1P).
Summary of Contents for BSVQ36MVJU
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Page 13: ...Introduction SiUS30 604 xii ...
Page 27: ...Capacity Range SiUS30 604 14 General Information ...
Page 49: ...Specifications SiUS30 604 36 Specifications ...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Page 309: ...SiUS39 601 iv Index ...