SiUS30-604
Troubleshooting by Indication on the Remote Controller
Troubleshooting
193
2.27
“
JC
”
Outside Unit:
Malfunction of Suction Pipe Pressure Sensor
Remote
Controller
Display
JC
Applicable
Models
RWEYQ60, 72, 84MTJU
Method of
Malfunction
Detection
Malfunction is detected from pressure detected by low pressure sensor.
Malfunction
Decision
Conditions
When the suction pipe pressure sensor is short circuit or open circuit.
Supposed
Causes
Defect of low pressure sensor system
Connection of high pressure sensor with wrong connection.
Defect of outside unit PC board.