Refrigerant Circuit
SiUS30-604
38
Refrigerant Circuit
1. Refrigerant Circuit
1.1
RWEYQ60MTJU / RWEYQ72MTJU / RWEYQ84MTJU
No. in
refrigerant
system
diagram
Symbol
Name
Major Function
A
M1C
Inverter compressor (INV)
Inverter compressor is operated on frequencies between 52 Hz and 230 Hz by
using the inverter. The number of operating steps is as follows.
E
Y1E
Electronic expansion valve
(Main: EV1)
In cooling operation: High pressure control
In heating or simultaneous cooling/heating operation:
When the heat exchanger is used as the evaporator : SH control
When the heat exchanger is used as the condenser : High pressure control
G
Y3E
Electronic expansion valve
(Subcool: EV3)
PI control is applied to keep the outlet superheated degree of sub-cooling heat
exchanger constant.
H
Y1S
Solenoid valve (Hot gas: SVP)
Used to prevent the low pressure from transient falling.
I
Y2S
Solenoid valve (Oil return of water
heat exchanger: SVE)
Used to collect the refrigerant oil from water heat exchanger.
J
Y3S
Solenoid valve (Receiver gas
charging: SVL)
Used to maintain high pressure while in cooling operation at low water
temperature. And also used to prevent the accumulation of refrigerant in non-
operating outside units in the case of multiple-outside-unit system.
K
Y4S
Solenoid valve (Receiver gas
discharging: SVG)
Used to collect refrigerant to receiver.
M
Y5S
4-way selector valve
(Main: 20S1)
Changes the operation into cooling, heating or simultaneous cooling/heating
operation.
O
Y6S
Solenoid valve (Non-operating unit
liquid pipe closing: SVSL)
Used to prevent the accumulation of refrigerant in non-operating outside units in
the case of multiple-outside-unit system.
P
Y7S
4-way selector valve
(Sub: 20S2)
Changes the water heat exchanger into condenser or evaporator.
Q
S1NPH High pressure sensor
Used to detect high pressure.
R
S2NPL
Low pressure sensor
Used to detect low pressure.
S
S1PH
HP pressure switch
(For INV compressor)
In order to prevent the increase of high pressure when a malfunction occurs, this
switch is activated at high pressure of 580psi or more to stop the compressor
operation.
V
–
Fusible plug
In order to prevent the increase of pressure when abnormal heating is caused by
fire or others, the fusible part of the plug is molten at a temperature of 158 to
167°F to release the pressure into the atmosphere.
W
–
Pressure regulating valve 1 (Liquid
pipe to discharge pipe)
This valve opens at a pressure of 580psi or more for prevention of pressure
increase, thus resulting in no damage of functional parts due to the increase of
pressure in transportation or storage.
2
R2T
Thermistor (Suction pipe: Ts)
Used to detect suction pipe temperature, keep the suction superheated degree
constant in heating operation, and others.
3
R3T
Thermistor (INV discharge pipe: Tdi)
Used to detect discharge pipe temperature, make the temperature protection
control of compressor, and others.
6
R4T
Thermistor (Heat exchanger gas pipe:
Tg)
Used to detect gas pipe temperature of water heat exchanger.
7
R5T
Thermistor (Sub-cooling heat
exchanger outlet pipe: Tsh)
Used to detect gas pipe temperature on the evaporation side of sub-cooling heat
exchanger, keep the superheated degree at the outlet of sub-cooling heat
exchanger constant, and others.
8
R6T
Thermistor (Receiver outlet liquid
pipe: Tl)
Used to detect receiver outlet liquid pipe temperature, prevent the drift between
outdoor units while in heating operation in the case of multiple-outside-unit
system, and others.
Summary of Contents for BSVQ36MVJU
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Page 13: ...Introduction SiUS30 604 xii ...
Page 27: ...Capacity Range SiUS30 604 14 General Information ...
Page 49: ...Specifications SiUS30 604 36 Specifications ...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Page 309: ...SiUS39 601 iv Index ...