Troubleshooting by Remote Controller
SiUS30-604
146
Troubleshooting
Mode
No
Function
Contents and operation method
Remote controller display example
40
Malfunction
hysteresis display
Display malfunction hysteresis.
The history No. can be changed with the
button.
41
Display of sensor
and address data
Display various types of data.
Select the data to be displayed with the
button. Sensor data
0: Thermostat sensor in remote controller.
1: Suction
2: Liquid pipe
3: Gas pipe
Address data
4: Indoor unit address
5: Outside unit address
6: BS unit address
7: Zone control address
8: Cool/heat group address
9: Demand / low noise address
43
Forced fan ON
Manually turn the fan ON by each unit. (When
you want to search for the unit No.)
By selecting the unit No. with the
button,
you can turn the fan of each indoor unit on
(forced ON) individually.
44
Individual setting
Set the fan speed and air flow direction by each
unit
Select the unit No. with the time mode
button. Set the fan speed with the
button.
Set the air flow direction with the
button.
45
Unit No. transfer
Transfer unit No.
Select the unit No. with the
button.
Set the unit No. after transfer with the
button.
46
This function is not used by VRV R-410A Heat Pump 50Hz.
47
Hystory No: 1 - 9
1: Latest
Unit 1
Malfunction code
2-U4
Malfunction code
40
(VE007)
Temperature ºC
41
Sensor data display
Unit No.
Sensor type
1 1
2 7
Address
41
Address display
Unit No.
Address type
1 8
1
(VE008)
Unit 1
43
(VE009)
Unit 1
Code
44
Air flow direction
P0 - P4
1 3
(VE010)
Fan speed 1: low
3: High
Unit 1
Code
45
Present unit No.
Unit No. after
transfer
0 2
(VE011)
Summary of Contents for BSVQ36MVJU
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Page 13: ...Introduction SiUS30 604 xii ...
Page 27: ...Capacity Range SiUS30 604 14 General Information ...
Page 49: ...Specifications SiUS30 604 36 Specifications ...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Page 309: ...SiUS39 601 iv Index ...