SiUS30-604
Troubleshooting by Indication on the Remote Controller
Troubleshooting
179
2.17
“
E9
”
Outside Unit:
Malfunction of Moving Part of Electronic
Expansion Valve (Y1E, Y3E)
Remote
Controller
Display
E9
Applicable
Models
RWEYQ60, 72, 84MTJU
Method of
Malfunction
Detection
Check disconnection of connector
Check continuity of expansion valve coil
Malfunction
Decision
Conditions
Error is generated under no common power supply when the power is on.
Supposed
Causes
Defect of moving part of electronic expansion valve
Defect of outside unit PC board (A1P)
Defect of connecting cable
Troubleshooting
(V3067)
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Return to normal?
Turn power supply off, and
turn power supply on again.
Electronic
expansion valve is
connected to X26A and
X28A of outside unit
PC board
(A1P).
Normal
when coil
check (
∗
1) of the moving
part of the electronic
expansion valve is
checked.
The connecting
cable is short-circuited or
disconnected.
Replace the connecting cable.
Replace outside unit PC board
A1P.
NO
NO
NO
NO
Replace the moving part of the
electronic expansion valve.
External factor other than
malfunction (for example, noise
etc.).
After connecting, turn the power
off and then back on again.
YES
YES
YES
Summary of Contents for BSVQ36MVJU
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Page 13: ...Introduction SiUS30 604 xii ...
Page 27: ...Capacity Range SiUS30 604 14 General Information ...
Page 49: ...Specifications SiUS30 604 36 Specifications ...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Page 309: ...SiUS39 601 iv Index ...