SiUS30-604
Troubleshooting by Indication on the Remote Controller
Troubleshooting
155
2.2
“
A1
”
Indoor Unit:
PC Board Defect
Remote
Controller
Display
A1
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Check data from E²PROM.
Malfunction
Decision
Conditions
When data could not be correctly received from the E²PROM
E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power supply is
turned off.
Supposed
Causes
Defect of indoor unit PC board
Troubleshooting
Turn power supply OFF, then
power ON again.
Does
the system return
to normal?
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
External factor other than
malfunction (for example,
noise etc.).
Replace the indoor unit PC
board.
(V2777)
NO
Summary of Contents for BSVQ36MVJU
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Page 13: ...Introduction SiUS30 604 xii ...
Page 27: ...Capacity Range SiUS30 604 14 General Information ...
Page 49: ...Specifications SiUS30 604 36 Specifications ...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Page 309: ...SiUS39 601 iv Index ...