Procedure for Mounting / Dismounting of Switch Box
SiUS30-604
256
Procedure for Mounting / Dismounting of Switch Box
1. Procedure for Mounting / Dismounting of Switch
Box
1.1
Procedure for Dismounting
1. Dismount the lid from the switch box.
2. Disconnect high voltage and low voltage wirings from the PC board and the terminal blocks,
referring to Figure on the right.
3. Unscrew mounting screws from the top plate, the stop valve mounting plate, and the bottom
frame in a total of 6 places.
4. With attention paid not to make the switch box support leg into contact with the side panel,
rotate the switch box to pull out it, while referring to Figure on the right.
In order to pull out the switch box, check to be sure no wirings get stuck with the switch box.
Procedure for Mounting/Dismounting of Switch Box
1.2
Procedure for Mounting
Mount the switch box, following the procedure for dismounting in reverse.
After the completion of mounting, check to be sure connectors are all properly connected.
Summary of Contents for BSVQ36MVJU
Page 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz ...
Page 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v ...
Page 13: ...Introduction SiUS30 604 xii ...
Page 27: ...Capacity Range SiUS30 604 14 General Information ...
Page 49: ...Specifications SiUS30 604 36 Specifications ...
Page 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit ...
Page 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338 ...
Page 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A ...
Page 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A ...
Page 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A ...
Page 309: ...SiUS39 601 iv Index ...