7/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Official Value
Installer setting at variance with
default value
Field settings table
9.9.B
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.C
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.9.D
[4-01]
0: None
1: BSH
2: BUH
9.9.F
[7-07]
R/W
0: Disabled
1: Enabled
└─ Energy metering
9.A.1
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.A.2
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
└─ Sensors
9.B.1
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
9.B.2
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
9.B.3
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─ Bivalent
9.C.1
[C-02]
R/W
0: No
1: Bivalent
9.C.2
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.C.3
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.C.4
[C-04]
R/W
2~10°C, step 1°C
3°C
Installer settings
9.D
[C-09]
R/W
0: Normally open
1: Normally closed
9.E
[3-00]
R/W
0: No
1: Yes
9.F
[E-08]
R/W
0: disabled
1: Enabled
9.G
R/W
0: No
1: Yes
└─ Overview field settings
9.I
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
9.I
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
9.I
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-03]
R/W
-40~5°C, step: 1°C
-15°C
9.I
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
9.I
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
9.I
[0-06]
R/W
25~43°C, step: 1°C
35°C
9.I
[0-07]
R/W
10~25°C, step: 1°C
20°C
9.I
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55°C
9.I
[0-0C]
R/W
45~[6-0E]°C, step: 1°C
60°C
9.I
[0-0D]
R/W
10~25°C, step: 1°C
15°C
9.I
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
9.I
[1-00]
R/W
-40~5°C, step: 1°C
-15°C
9.I
[1-01]
R/W
10~25°C, step: 1°C
15°C
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Auto restart
Power saving function
Disable protections
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Averaging time
Bivalent
Boiler efficiency
Temperature
Hysteresis
Alarm output
Limit 4
Priority heater
Electricity meter 1
Electricity meter 2
External sensor
Ext. amb. sensor offset
BBR16 activation (#)
Limit 3
(*1) *6V_(*2) *9W_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*
(#) Only applicable in Swedish language.
4P586458-1 - 2019.07
Summary of Contents for Altherma 3 H HT EPRA14DAW1
Page 258: ......
Page 259: ......
Page 260: ...4P587502 1A 2020 01 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...