4/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Official Value
Installer setting at variance with
default value
Field settings table
└─ Disinfection
5.7.1
[2-01]
R/W
0: No
1: Yes
5.7.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
5.7.3
[2-02]
R/W
0~23 hour, step: 1 hour
1
5.7.4
[2-03]
R/W
[E-07]≠
1 :
55~75°C, step: 5°C
70°C
[E-07]=1 :
60°C
60°C
5.7.5
[2-04]
R/W
[E-07]≠1: 5~60 min, step: 5 min
10 min
[E-07]=1: 40~60 min, step: 5 min
40 min
Tank
5.8
[6-0E]
R/W
(*3) [E-07]=0:
40~75°C, step: 1°C
60°C
(*3) [E-07]=5:
40~80°C, step: 1°C
80°C
(*4) : 40~65°C, step: 1°C
65°C
5.9
[6-00]
R/W
2~40°C, step: 1°C
8°C
5.A
[6-08]
R/W
2~20°C, step: 1°C
10°C
5.B
R/W
0: Fixed
1: Weather dependent
└─ WD curve
5.C
[0-0B]
R/W
35~[6-0E]°C, step: 1°C
55°C
5.C
[0-0C]
R/W
45~[6-0E]°C, step: 1°C
60°C
5.C
[0-0D]
R/W
10~25°C, step: 1°C
15°C
5.C
[0-0E]
R/W
-40~5°C, step: 1°C
-10°C
Tank
5.D
[6-01]
R/W
0~10°C, step: 1°C
2°C
5.E
R/O
0: 2-points
1: Slope-Offset
User settings
└─ Quiet
7.4.1
R/W
0: OFF
1: Manual
2: Automatic
7.4.3
R/W
0: Quiet
1: More Quiet
2: Most Quiet
└─ Electricity price
7.5.1
R/W
0,00~990/kWh
1/kWh
7.5.2
R/W
0,00~990/kWh
1/kWh
7.5.3
R/W
0,00~990/kWh
1/kWh
User settings
7.6
R/W
0,00~990/kWh
0,00~290/MBtu
1,0/kWh
Installer settings
└─ Configuration wizard
└─ System
9.1.3.2
[E-03]
R/O
3: 6V (*1)
4: 9W (*2)
9.1.3.3
[E-05]
[E-06]
[E-07]
R/W
No DHW (*3)
EKHW (*3)
Integrated (*4)
EKHWP (*3)
9.1.3.4
[4-06]
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
9.1.3.5
[7-02]
R/W
0: Single zone
1: Dual zone
9.1.3.6
[E-0D]
R/W
0: No
1: Yes
9.1.3.7
[6-02]
R/W
0~10kW, step: 0,2kW
3kW (*3)
0kW (*4)
└─ Backup heater
9.1.4.1
[5-0D]
R/W (*1)
R/O (*2)
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
9.1.4.2
[4-0A]
R/W
0: 1
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.1.4.3
[6-03]
R/W
0~10kW, step: 0,2kW
2
kW (*1)
3kW (*2)
Activation
Number of zones
Voltage
Configuration
Capacity step 1
Glycol Filled system
BSH capacity (*3)
Margin
Activation
High
Medium
Low
WD curve type
Level
Gas price
BUH type
Domestic hot water
Start time
Setpoint mode
Leaving water value for high ambient temp. for DHW WD curve.
Operation day
Reheat hysteresis
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
Emergency
Duration
Tank setpoint
Hysteresis
Maximum
4P586458-1 - 2019.07