9
|
Configuration
Installer reference guide
180
EPRA14~W1 + ETVH/9W(G)
Daikin Altherma 3 H HT F
4P587502-1A – 2020.01
Emergency
Emergency
To keep energy consumption low, we recommend to set
Emergency
to
auto SH
reduced/DHW off
if the house is unattended for longer periods.
#
Code
Description
[9.5.1]
[4-06]
▪
0:
Manual
▪
1:
Automatic
▪
2:
auto SH reduced/DHW on
▪
3:
auto SH reduced/DHW off
▪
4:
auto SH normal/DHW off
INFORMATION
The auto emergency setting can be set in the menu structure of the user interface
only.
INFORMATION
If a heat pump failure occurs and
Emergency
is set to
Manual
, the room frost
protection function, the underfloor heating screed dryout function, and the water
pipe antifreeze function will remain active even if the user does NOT confirm
emergency operation.
HP forced off
HP forced off
mode can be activated to allow the backup heater to provide
domestic hot water and space heating. Cooling is NOT possible when this mode is
activated.
#
Code
Description
[9.5.2]
[7-06]
Activation of the
HP forced off
mode:
▪
0:
disabled
▪
1:
enabled
Glycol filled system
Glycol Filled system
This setting gives the installer the possibility to indicate whether the system is filled
with glycol or water. This is important in case glycol is used to protect the water
circuit against freezing. If NOT set correctly, the liquid in the piping can freeze.
#
Code
Description
N/A
[E-0D]
Glycol Filled system
: Is the system filled
with glycol?
▪
0:
No
▪
1:
Yes
Balancing
Priorities
For systems with an integrated domestic hot water tank.