3/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Official Value
Installer setting at variance with
default value
Field settings table
└─ Heating WD curve
3.5
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
3.5
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
3.5
[0-02]
R/W
10~25°C, step: 1°C
15°C
3.5
[0-03]
R/W
-40~5°C, step: 1°C
-15°C
└─ Cooling WD curve
3.6
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
3.6
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
3.6
[0-06]
R/W
25~43°C, step: 1°C
35°C
3.6
[0-07]
R/W
10~25°C, step: 1°C
20°C
Additional zone
3.7
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─ Setpoint range
3.8.1
[9-05]
R/W
15~37°C, step: 1°C
25°C
3.8.2
[9-06]
R/W
[2-0D]=2:
37~70, step: 1°C
70
°C
[2-0D]≠2:
37~55, step: 1°C
55°C
3.8.3
[9-07]
R/W
5~18°C, step: 1°C
7°C
3.8.4
[9-08]
R/W
18~22°C, step: 1°C
22°C
Additional zone
3.A
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
└─ Delta T
3.B.1
[1-0C]
R/W
3~10°C, step: 1°C
10°C
3.B.2
[1-0E]
R/W
3~10°C, step: 1°C
5°C
Additional zone
3.C
R/O
0: 2-points
1: Slope-Offset
Space heating / cooling
└─ Operation range
4.3.1
[4-02]
R/W
14~35°C, step: 1°C
35°C
4.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C
Space heating / cooling
4.4
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
4.5
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
4.6
[E-02]
R/W (*5)
R/O (*6)
0: Reversible (*5)
1: Heating only (*6)
4.7
[9-0D]
R/W
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
Space heating / cooling
4.9
[F-00]
R/W
0: Restricted
1: Allowed
4.A
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
4.B
[9-04]
R/W
1~4°C, step: 1°C
1°C
4.C
[2-06]
R/W
0: Disabled
1: Enabled
Tank
5.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
5.3
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.4
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
5.6
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
Antifrost
Reheat setpoint
Eco setpoint
Low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Unit type
Increase around 0°C
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
Pump operation mode
Pump outside range
Emitter type
Low ambient temp. for LWT add zone cooling WD curve.
Heating minimum
Heating maximum
Delta T cooling
Pump limitation
Number of zones
Overshoot
Cooling minimum
Cooling maximum
Space cooling OFF temp
Thermostat type
High ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
Delta T heating
Space heating OFF temp
WD curve type
Comfort setpoint
Heat up mode
(*1) *6V_(*2) *9W_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*