8
|
Electrical installation
Installer reference guide
106
EPRA14~W1 + ETVH/9W(G)
Daikin Altherma 3 H HT F
4P587502-1A – 2020.01
Model (power supply)
Connections to backup heater power supply
*9W (3N~ 400 V)
3N~, 50 Hz
400 V AC
SWB
Q1DI
L1 L2 L3 N
1
2
3
4
5
6
7
8
F1B
I
I
I
I
X6M
2
1
K5M
4
3
6
5
14
13
BRN
GRY
BLK
BLU
F1B Overcurrent fuse (field supply). Recommended fuse: 4‑pole; 20 A;
curve 400 V; tripping class C.
K5M Safety contactor (in the lower switch box)
Q1DI Earth leakage circuit breaker (field supply)
SWB Switch box
X6M Terminal (field supply)
NOTICE
Do NOT cut or remove the backup heater power supply cable.
8.3.3 To connect the shut-off valve
INFORMATION
Shut-off valve usage example.
In case of one LWT zone, and a combination of
underfloor heating and heat pump convectors, install a shut-off valve before the
underfloor heating to prevent condensation on the floor during cooling operation.
For more information, see the installer reference guide.
Wires: 2×0.75 mm²
Maximum running current: 100 mA
230 V AC supplied by PCB
[2.D]
Shut off valve
1
"6.2.5 To open the indoor unit"
61]):
1
Top panel
1
2
3
2
User interface panel
3
Upper switch box cover
2
Connect the valve control cable to the appropriate terminals as shown in the
illustration below.
Summary of Contents for Altherma 3 H HT EPRA14DAW1
Page 258: ......
Page 259: ......
Page 260: ...4P587502 1A 2020 01 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...