8/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Official Value
Installer setting at variance with
default value
Field settings table
9.I
[1-02]
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
9.I
[1-03]
R/W
[9-01]~min(45, [9-00])°C , step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
9.I
[1-04]
R/W
0: Disabled
1: Enabled
9.I
[1-05]
R/W
0: Disabled
1: Enabled
9.I
[1-06]
R/W
10~25°C, step: 1°C
20°C
9.I
[1-07]
R/W
25~43°C, step: 1°C
35°C
9.I
[1-08]
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
9.I
[1-09]
R/W
[9-03]~[9-02]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
9.I
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
9.I
[1-0B]
R/W
3~10°C, step: 1°C
5°C
9.I
[1-0C]
R/W
3~10°C, step: 1°C
10°C
9.I
[1-0D]
R/W
3~10°C, step: 1°C
5°C
9.I
[1-0E]
R/W
3~10°C, step: 1°C
5°C
9.I
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
9.I
[2-01]
R/W
0: No
1: Yes
9.I
[2-02]
R/W
0~23 hour, step: 1 hour
1
9.I
[2-03]
R/W
[E-07]≠
1 :
55~75°C, step: 5°C
70°C
[E-07]=1 :
60°C
60°C
9.I
[2-04]
R/W
[E-07]≠1: 5~60 min, step: 5 min
10 min
[E-07]=1: 40~60 min, step: 5 min
40 min
9.I
[2-05]
R/W
4~16°C, step: 1°C
8°C
9.I
[2-06]
R/W
0: Disabled
1: Enabled
9.I
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
9.I
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.I
[2-0E]
R/W
0~50 A, step: 1 A
50 A
9.I
[3-00]
R/W
0: No
1: Yes
9.I
[3-01]
0
9.I
[3-02]
1
9.I
[3-03]
4
9.I
[3-04]
2
9.I
[3-05]
1
9.I
[3-06]
R/W
18~30°C, step: 0,5°C
30°C
9.I
[3-07]
R/W
12~18°C, step: 0,5°C
12°C
9.I
[3-08]
R/W
25~35°C, step: 0,5°C
35°C
9.I
[3-09]
R/W
15~25°C, step: 0,5°C
15°C
9.I
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
What is the maximum allowed current over the heatpump ?
--
Is auto restart of the unit allowed?
--
What is the disinfection target temperature?
What emitter type is connected to the main LWT zone?
What emitter type is connected to the additional LWT zone?
What is the minimum desired room temperature in cooling?
How long must the tank temperature be maintained?
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
Low ambient temp. for LWT main zone cooling WD curve.
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
What is the mimimum desired room temperature in heating?
What is the maximum desired room temperature in cooling?
What is the BUH operation mode?
--
--
--
What is the maximum desired room temperature in heating?
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Weather dependent cooling of the main leaving water temperature zone.
Weather dependent cooling of the additional leaving water temperature zone
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
What is the averaging time for the outdoor temp?
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
What is the desired delta T in heating for the main zone?
What is the desired delta T in cooling for the main zone?
What is the desired delta T in cooling for the additional zone?
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
What is the desired delta T in heating for the additional zone?
4P586458-1 - 2019.07
(#) Only applicable in Swedish language.
(*1) *6V_(*2) *9W_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*
Summary of Contents for Altherma 3 H HT EPRA14DAW1
Page 258: ......
Page 259: ......
Page 260: ...4P587502 1A 2020 01 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...