Chapter 5: Expansion Box and Virtual Expansion Box Installation
NOTE:
We recommend using one box ID per electrical panel where modules are installed. Each module
will have the same box ID, but a different slot number.
NOTE:
A maximum of 8 modules can have the same box ID. For example, if the electrical panel contains
18 modules, 3 box IDs must be used: one for modules 1 to 8, a second one for modules 9 to 16,
and a last one for module 17 and 18.
NOTE:
The box IDs of the modules are displayed on the EDGE once they are detected.
NOTE:
Consult the cabinet’s manual about how to seal it.
DC Network and Power Supply Redundancy
EDGE system uses redundant supply.
Refer to the Networking Chapter to understand the supply redundancy concept. In the supply redundancy
concept, the subgroup concept is very important. Depending on the DC network chosen, select the right
wiring diagram for installation.
EDGE 4IN-2V-8DO NOTE : The same configurations are available on the EDGE 4IN-2V-8DO. The power
supply redundancy concept is the same than an Expansion Box.
68
890–00687
EDGE 2
Summary of Contents for 064-11343
Page 7: ...Chapter 1 Introduction Figure 1 2 Enclosure Identification 890 00687 EDGE 2 7...
Page 22: ...NOTES 22 890 00687 EDGE 2...
Page 30: ...Chapter 2 Pre Installation Planning 30 890 00687 EDGE 2...
Page 40: ...NOTES 40 890 00687 EDGE 2...
Page 58: ...NOTES 58 890 00687 EDGE 2...
Page 98: ...NOTES 98 890 00687 EDGE 2...
Page 112: ...NOTES 112 890 00687 EDGE 2...
Page 116: ...NOTES 116 890 00687 EDGE 2...
Page 120: ...NOTES 120 890 00687 EDGE 2...
Page 134: ...NOTES 134 890 00687 EDGE 2...
Page 135: ...F Extending a cable Best practice using a junction box 890 00687 EDGE 2 135...
Page 136: ...Appendix F Extending a cable Using of heat shrink tubing 136 890 00687 EDGE 2...