Appendix C: Technical Specifications
Clearance
Top
300mm (12 inches)
Bottom
300mm (12 inches)
Hinge Side
250mm (10 inches)
Latch Side
180mm (7 inches)
EDGE 6-Slot Expansion Box - dimensions and weight
Enclosure
dimensions
Height
660 mm (26 inches)
Width
635 mm (25 inches)
Depth
279 mm (11 inches)
Weight
15966 grams (35.2 lbs)
Clearance around
the enclosure
Top
300mm (12 inches)
Bottom
300mm (12 inches)
Hinge Side
250mm (10 inches)
Latch Side
180mm (7 inches)
Table C-7
Edge 4IN-2V-8DO dimensions and weight
Dimensions
Height
77.12mm (3.04 inches)
Width
144.16mm (5.67inches)
Depth
340.2mm (13.4 inches)
Weight
680.39 grams (1.5 lbs)
Table C-8
6-Slot Expansion Box and 3-Slot Expansion Box ratings
6-Slot
100Vac-240Vac, ±10%,50-60Hz, 1 phase, 120W
3-Slot
100Vac-240Vac ±10%; 50-60Hz, 1 phase, 120W
On/Off outputs
NO (normally open) contact - motor/inductive load
12A MAX
(Nb of Units = Max current rating divided by the max cur-
rent of the fan multiplied by its service factor )
Ex.: 12A /(2.5 A * 1.5 SF) = 3.2, relay can drive 3 fans
Minimum load of 0.2A
NO (Normally Opened) contact - resistive load (elec-
tric heating element)
120/208/240Vac: 12A MAX
Minimum load of 0.2A
NO (Normally Opened) contact - Tungsten load
(incandescent and heat lamp)
120Vac; 5A MAX
208Vac; 5A MAX
240Vac; 5A MAX
Minimum load of 0.2A
NO (Normally Opened) contact - DC load
24Vdc; 5A MAX. ( Current reading not available in DC).
Minimum load of 0.2A
NO (normally opened) contact - LED and CCFL loads
120/208/240Vac, 750W; 920VA MAX
124
890–00687
EDGE 2
Summary of Contents for 064-11343
Page 7: ...Chapter 1 Introduction Figure 1 2 Enclosure Identification 890 00687 EDGE 2 7...
Page 22: ...NOTES 22 890 00687 EDGE 2...
Page 30: ...Chapter 2 Pre Installation Planning 30 890 00687 EDGE 2...
Page 40: ...NOTES 40 890 00687 EDGE 2...
Page 58: ...NOTES 58 890 00687 EDGE 2...
Page 98: ...NOTES 98 890 00687 EDGE 2...
Page 112: ...NOTES 112 890 00687 EDGE 2...
Page 116: ...NOTES 116 890 00687 EDGE 2...
Page 120: ...NOTES 120 890 00687 EDGE 2...
Page 134: ...NOTES 134 890 00687 EDGE 2...
Page 135: ...F Extending a cable Best practice using a junction box 890 00687 EDGE 2 135...
Page 136: ...Appendix F Extending a cable Using of heat shrink tubing 136 890 00687 EDGE 2...