Chapter 5: Expansion Box and Virtual Expansion Box Installation
WARNING
If the disconnect switch or the circuit breaker is used as a sectioning device, the
device must be correctly identified with which function of the controller opens the
circuit. The Off or Stop and On position must be clearly identified on the sectioning
device.
It is recommended to use a DPST disconnecting switch in series with a breaker. In the case of
the use of a SPST disconnecting switch, connect the SPST disconnecting switch to cut the hot
line with a neutral circuit case.
IMPORTANT:
The SPST disconnecting switch circuit is allowed only in North America under 120Vac.
Over 120Vac in North America and whatever the voltage in International markets, only the
DPST disconnecting switch is allowed.
NOTE:
A minimum wire gauge of 14 AWG (diameter of 1.63mm or cross sectional area of 2.08mm
2
) is
required for proper operation. The maximum current rating of each zone allowed is 8.0A. The min-
imum temperature insulation is 90 °C. A voltage insulation of 300V is recommended.
NOTE:
The maximum breaker value per zone is 15 Amps max.
NOTE:
Refer to local and national electrical codes.
NOTICE
For the big terminal blocks used for AC inputs, use a tightening torque from 0.7N*m
(6.2lbf*in) to 0.8N*m (7lbf*in) to fasten a wire gage from 10AWG (diameter of 2.58mm
or cross sectional area of 5.26mm2) to 14AWG (diameter of1.62mm or cross
sectional area of 2.08mm2).
WARNING
Installation must only be performed by qualified service personnel.
DANGER
Disconnect supply before servicing.
1. From an electrical distribution panel in series with disconnecting switches, follow the wiring diagram
to connect the main voltage supply to the system’s main inputs for each zone.
2. Open the disconnecting switches or breaker before wiring.
3. Plug the wires (L1 to L1, L2/N to L2/N) to the for each zone.
890–00687
EDGE 2
77
Summary of Contents for 064-11343
Page 7: ...Chapter 1 Introduction Figure 1 2 Enclosure Identification 890 00687 EDGE 2 7...
Page 22: ...NOTES 22 890 00687 EDGE 2...
Page 30: ...Chapter 2 Pre Installation Planning 30 890 00687 EDGE 2...
Page 40: ...NOTES 40 890 00687 EDGE 2...
Page 58: ...NOTES 58 890 00687 EDGE 2...
Page 98: ...NOTES 98 890 00687 EDGE 2...
Page 112: ...NOTES 112 890 00687 EDGE 2...
Page 116: ...NOTES 116 890 00687 EDGE 2...
Page 120: ...NOTES 120 890 00687 EDGE 2...
Page 134: ...NOTES 134 890 00687 EDGE 2...
Page 135: ...F Extending a cable Best practice using a junction box 890 00687 EDGE 2 135...
Page 136: ...Appendix F Extending a cable Using of heat shrink tubing 136 890 00687 EDGE 2...