3-Slot or 6-Slot Expansion Box
Figure 10-2
PCB422 in an expansion box enclosure
1
Safety network activity LED’s
2
Automation network activity LED’s
3
F1 & F2
Safety network fuses
F3 & F4
Automation network fuses
The 3 or 6-Slot Expansion
Box doesn’t power on
Verify if wires are connected from the Panel Mount Power Supply to the Backplane
(PCB-420 and PCB-421)
Verify if wires from the main voltage supply are connected to the Panel Mount
Power Supply
Verify if wires are connected at the right terminals
Measure the voltage between the terminal 24V and GND. The voltage must be at
least 24V
If the problem persists, contact AP/Cumberland or GSI Electronics
The 3 or 6-Slot Expansion
Box does not communi-
cate with the EDGE 2
Controller or other Expan-
sion Box without power
supply
Verify if the Expansion Box is powered up
Verify if there are activities on the bus communication by looking at the activities
LED’s on PCB-422
Verify if F1, F2, F3 or F4 on PCB422 are not blown.
Verify if the network link is installed correctly: Terminal A from Expansion Box to x
Slots Expansion Box terminal A, Terminal B from Expansion Box to x Slots Expan-
sion Box terminal B
Verify if the network communication is installed in daisy chain.
890–00687
EDGE 2
105
Summary of Contents for 064-11343
Page 7: ...Chapter 1 Introduction Figure 1 2 Enclosure Identification 890 00687 EDGE 2 7...
Page 22: ...NOTES 22 890 00687 EDGE 2...
Page 30: ...Chapter 2 Pre Installation Planning 30 890 00687 EDGE 2...
Page 40: ...NOTES 40 890 00687 EDGE 2...
Page 58: ...NOTES 58 890 00687 EDGE 2...
Page 98: ...NOTES 98 890 00687 EDGE 2...
Page 112: ...NOTES 112 890 00687 EDGE 2...
Page 116: ...NOTES 116 890 00687 EDGE 2...
Page 120: ...NOTES 120 890 00687 EDGE 2...
Page 134: ...NOTES 134 890 00687 EDGE 2...
Page 135: ...F Extending a cable Best practice using a junction box 890 00687 EDGE 2 135...
Page 136: ...Appendix F Extending a cable Using of heat shrink tubing 136 890 00687 EDGE 2...