Appendix D: Low Voltage Cable Specifications
Table D-2
DC Power cables (Signal 24V and signal GND)
Parameter
Wire gage when a load of 24W (max 1.5A) is connected between the source and the
load in a non-redundant system
Wire gauge
18 AWG
(diam-
eter of 1.02mm
or cross sec-
tional area of
0.82mm²)
16* AWG
(diam-
eter of 1.29mm
or cross sec-
tional area of
1.30mm²)
14 AWG
(diam-
eter of 1.62mm
or cross sec-
tional area of
2.08mm²)
12 AWG
(diam-
eter of 2.05mm
or cross sec-
tional area of
3.30mm²)
10 AWG
(diam-
eter of 2.58mm
or cross sec-
tional area of
5.26mm²)
1 pair twisted
shielded
1 pair twisted
shielded
1 pair twisted
shielded
1 pair twisted
shielded
1 pair twisted
shielded
Max. length
150m (500 ft.)
150m (500 ft.)
300m (1000 ft.)
600m (2000 ft.)
1200m (4000
ft.)
Inductance
Nominal
(typical)
0.17 μH/ft
0.174 μH/ft
0.16 μH/ft
0.16 μH/ft
0.14 μH/ft
Conductor DCR
@20°C, Nomi-
nal (typical)
6.1 Ω/1000ft
3.6 Ω/1000ft
2.6 Ω/1000ft
1.63 Ω/1000ft
1.09 Ω/1000ft
Certification and
type
CSA,CIC (TC-ER) FT4 type, 16AWG, 600V, 194˚F (minimum 90˚C)
UL, TC-ER FT4 type, 16AWG, 600V, 194˚F (minimum 90˚C)
Maximum
Jacket
diameter*
0.449 inch
* Some products are provided with strain reliefs. If the cable diameter goes over this diameter value, the strain reliefs may not
work properly.
WARNING
Insulation on conductors must be rated for 600 Volts and 90°C (194°F).
NOTICE
EDGE network cables have to use class 1 load type. AP/Cumberland recommends
using TC-ER cable type.
NOTICE
Refer to the Wiring Methods and Materials section from the National Electric Code to
use the correct wire for the installation.
NOTICE
TC-ER conductors in sizes 18 AWG and 16 AWG shall be type FFH-2, KF-2, KFF-2,
PAF, PAFF, PF, PFF, PGF, PGFF, PTF, PTFF, RFH-2, RFHH-2, RFHH-3, SF-2, SFF-2, TF,
TFF, TFFN, TFN, ZF, or ZFF. Conductor with other types and thicknesses of
insulation shall be listed for Class 1 load circuit use.
AP/Cumberland can provide sourced color-coded communication wire to install EDGE controls. The wire
will be available in both 16 and 18 gauge to accommodate the specified distance between controls (as
shown above). The communication wire is available in one or two twisted shielded pairs, and with two dif-
ferent outside jacket colors (red and black.) Black-jacketed wire is to be used for the automation circuit
130
890–00687
EDGE 2
Summary of Contents for 064-11343
Page 7: ...Chapter 1 Introduction Figure 1 2 Enclosure Identification 890 00687 EDGE 2 7...
Page 22: ...NOTES 22 890 00687 EDGE 2...
Page 30: ...Chapter 2 Pre Installation Planning 30 890 00687 EDGE 2...
Page 40: ...NOTES 40 890 00687 EDGE 2...
Page 58: ...NOTES 58 890 00687 EDGE 2...
Page 98: ...NOTES 98 890 00687 EDGE 2...
Page 112: ...NOTES 112 890 00687 EDGE 2...
Page 116: ...NOTES 116 890 00687 EDGE 2...
Page 120: ...NOTES 120 890 00687 EDGE 2...
Page 134: ...NOTES 134 890 00687 EDGE 2...
Page 135: ...F Extending a cable Best practice using a junction box 890 00687 EDGE 2 135...
Page 136: ...Appendix F Extending a cable Using of heat shrink tubing 136 890 00687 EDGE 2...