Chapter 2: Pre-Installation Planning
• If the bedrock is more than 3 meters (10 feet) below ground level, drive the grounding rod vertically
3 meters (10 feet) into the ground.
• If the bedrock is more than 1.2 meters (47 inches) below ground level, drive the rod into the ground
to bedrock level and bury the remainder horizontally at least 0.6 meters (2 feet) below ground level.
• If the bedrock is less than 1.2 meters (47 inches) deep, bury the rod horizontally at least 0.6 meters
(2 feet) below ground level.
NOTE:
Refer to your local regulations and practices if an adequate grounding installation isn’t possible.
Rod Specifications for Grounding
The rod specifications are guidelines only. Refer to your national and local regulations for compliance
criteria.
Table 2-1
Grounding rod specifications
Item
Description
Material
Metallic, normally steel core.
Rod surface
The surface must be clean. It cannot be coated with paint, varnish or any non-conducting
substance.
Minimum diameter
16 mm (5/8 inches)
Minimum length
2440 mm (8 feet)
Cable Specifications for Grounding
The cable specifications are guidelines only. Refer to your national and local regulations for compliance
criteria.
Table 2-2
Grounding Cable Specifications
Item
Description
Certification and
type
CSA, TEW type.
UL, 1015 type, 12 AWG, 600 V, 105 °C (221 °F), green/yellow insulated wire.
Maximum length
15 meters (50 feet)
Suggested cable
Belden # 9912, color code 189, or equivalent
Installation Guidelines
Electrical Noise
• Install the controllers as far as possible from high voltage sources. It must be installed at least 24
inches (600mm) away from a Variable Frequency Drive (VFD).
• Never mount a power supply or transformer near the controllers. Allow at least 12 inches (300mm)
between them.
Cable Installation
• Ensure all cable entries are made through the bottom of the enclosures. Do not make holes through
the top or side panels of enclosure and be careful not to damage the electronic cards located inside
the enclosure when drilling.
• All incoming cables must connect directly to the terminals. No cabling should touch the side panels
or the top circuit board. Do not use the controller as a junction box.
34
890–00687
EDGE 2
Summary of Contents for 064-11343
Page 7: ...Chapter 1 Introduction Figure 1 2 Enclosure Identification 890 00687 EDGE 2 7...
Page 22: ...NOTES 22 890 00687 EDGE 2...
Page 30: ...Chapter 2 Pre Installation Planning 30 890 00687 EDGE 2...
Page 40: ...NOTES 40 890 00687 EDGE 2...
Page 58: ...NOTES 58 890 00687 EDGE 2...
Page 98: ...NOTES 98 890 00687 EDGE 2...
Page 112: ...NOTES 112 890 00687 EDGE 2...
Page 116: ...NOTES 116 890 00687 EDGE 2...
Page 120: ...NOTES 120 890 00687 EDGE 2...
Page 134: ...NOTES 134 890 00687 EDGE 2...
Page 135: ...F Extending a cable Best practice using a junction box 890 00687 EDGE 2 135...
Page 136: ...Appendix F Extending a cable Using of heat shrink tubing 136 890 00687 EDGE 2...