AUTO - A
Communication bus 1 - Signal A of RS485 communication
AUTO - B
Communication bus 1 - Signal B of RS485 communication
AUTO- GND
Communication bus 1 - Power supply return
SAFE- 24V
Communication bus 2 - power supply 24Vdc
SAFE - A
Communication bus 2 - Signal A of RS485 communication
SAFE - B
Communication bus 2 - Signal B of RS485 communication
SAFE-GND
Communication bus 2 - Power supply return
CS(x)
Analog inputs for current sensors
VAR(x)
0-10Vdc Analog outputs
GND(x) close to VAR
(x)
Returns for 0-10Vdc analog outputs
Functional Earth
Functional Ground Terminal primarily used for functional earth terminals which are gen-
erally associated with test and measurement circuits. These terminals are not for safety
earthing purposes but provide an earth reference point.
EDGE Variable Output
Terminal name
Description
L1
SSR high voltage input from the main sector (source)
L2/N
SSR high voltage input from the main sector (source) using for a reference
LOAD
SSR high voltage output using to control the load
0-10V & CS
SSR low voltage input : 0-10Vdc
And voltage output proportional to current flowing through
Protective Earth
Protective Earth Ground Terminal, Primarily used for protective earth terminals.
Terminal connected to conductive parts of a device for the purpose of safety
and is intended to be connected to an external system for protective grounding
890–00687
EDGE 2
119
Summary of Contents for 064-11343
Page 7: ...Chapter 1 Introduction Figure 1 2 Enclosure Identification 890 00687 EDGE 2 7...
Page 22: ...NOTES 22 890 00687 EDGE 2...
Page 30: ...Chapter 2 Pre Installation Planning 30 890 00687 EDGE 2...
Page 40: ...NOTES 40 890 00687 EDGE 2...
Page 58: ...NOTES 58 890 00687 EDGE 2...
Page 98: ...NOTES 98 890 00687 EDGE 2...
Page 112: ...NOTES 112 890 00687 EDGE 2...
Page 116: ...NOTES 116 890 00687 EDGE 2...
Page 120: ...NOTES 120 890 00687 EDGE 2...
Page 134: ...NOTES 134 890 00687 EDGE 2...
Page 135: ...F Extending a cable Best practice using a junction box 890 00687 EDGE 2 135...
Page 136: ...Appendix F Extending a cable Using of heat shrink tubing 136 890 00687 EDGE 2...