MAINTENANCE WITH Q&A
Page 5-6
GENERAL TROUBLESHOOTING PROCEDURES
Table 4. General Troubleshooting Procedures
PROBLEM
PROBABLE CAUSE
CORRECTIVE ACTION
Compressor will
not run
Conditioning system OFF
Turn ON conditioning system
No electrical power
Check facility circuit breaker
Wrong voltage applied to unit
Check voltage and correct
Compressor internal overload tripped
Will automatically reset when cooled
High/Low Limit tripped
Correct cause of limit condition, repair and reset
Control alarm energized
Motor failure
Check winding resistance and lead to ground
resistance
Motor shorted
Replace compressor
Circuit breaker may be tripped
Refer to section on Resetting a Circuit Breaker
Unit short
cycles
continuously
Gain setting too high
Decrease gain setting
Proportional band setting to low
Increase proportional band setting
Compressor low on refrigerant
Check refrigerant and charge if necessary
Compressor
dif
fi
cult to start
Wrong voltage applied to unit
Connect correct voltage
Defective run/start capacitor(s)
Replace capacitor(s)
Defective start relay
Replace start relay
Refrigeration overcharge
Recover and recharge
High load amps Low voltage
Check supply circuit
Electrical malfunctions
Check for proper wiring and correct compressor
capacitor
Check for grounds and measure winding resistance
Defective start relay
Check and replace
Low Amps
Low refrigerant
Check for leaks; charge system
Insuf
fi
cient
cooling effect
Refrigerant shortage
Repair leak and recharge
Frosted coil
Defrost and dry coil
Low air circulation
Check fan blade and shaft. Blade may have come off
Exceeding rated live load capacity
(See data sheets)
Reduce live load
Cooling coils obstructed
Remove obstruction or defrost
TXV defective
Replace valve
Solenoid coil burned out
Replace coil
Solenoid valve bad
Replace valve
Dirty condenser
Clean condenser
R-404A compressor frosting
Possible leak in R-508B/R-23. Check ambient
pressures
R-508B/R-23
Head Pressure
too high
Refrigerant overcharge
Recover excess refrigerant
Exceeding rated live load capacity
(See data sheets)
Reduce live load
Air in system
Recover, evacuate and recharge.
R-404A system short of gas
Repair leak and recharge
Summary of Contents for ZP 16
Page 1: ...Installation Operation Maintenance Manual ZP Series 56120 REV AH 10 2019...
Page 4: ...INTRODUCTION THIS PAGE INTENTIONALLY LEFT BLANK...
Page 6: ...CHAMBER LABELS MEANINGS THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...GENERAL DESCRIPTION Page 2 24 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 42: ...INSTALLATION Page 3 2 Figure 1 Transporting a Chamber...
Page 46: ...INSTALLATION Page 3 6 Table 2 Water Usage SI Units...
Page 62: ...OPERATION Page 4 14 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 82: ...MAINTENANCE WITH Q A Page 5 20 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 84: ...SERVICE PARTS WARRANTY Page 6 2 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 88: ...SYSTEM DIAGRAMS Page 9 4 THIS PAGE INTENTIONALLY LEFT BLANK...