EZT-570S User Manual
115
Figure 8-19 Digital Output Wiring
The digital outputs are potential free dry contacts divided between two common
headers. Each output is rated for 2A of current with a maximum of 8A per common
line. If all outputs are being used, the sum of the current must not exceed 8A.
Digital Output Specifications
Voltage Input
Maximum Load Current
2A/point
8A per common line
Minimum Switching Load
0.1mA/0.1Vdc (reference value)
Response Time
1.7 seconds maximum