44
F.
Clean Combustion Chamber
by vacuuming. Exercise
care to avoid damaging Base Insulation.
G.
Install Burners
by reversing procedures used to
remove burners. Verify Main Burners are properly
located on support bracket in Base Rear Panel, seated
on Main Burner Orifices, and secured with hitch pin
clips. Verify Main Burner with Pilot Bracket is in
proper location. See Table 13.
H.
Lubrication.
Manufacturers Instruction should be
followed on all parts installed on boiler requiring
lubrication. This includes type of lubricant to be used,
frequency of lubrication, and points to lubricate.
I.
Check operation.
Refer to Section VIII: System Start-
up.
Boiler Model
Pilot Located Between Burners*
16H-340
6 & 7
16H-410
6 & 7
16H-460
7 & 8
16H-505
8 & 9
*
Burners numbered left to right as viewed from front of boiler.
Table 13: Pilot Burner Location
Figure 48: Boiler Flueway Cleaning