29
E.
MegaStor Water Heater
(if used). May be used with
Intermittent Circulation only.
Refer to MegaStor Installation, Operating and
Service Instructions for wiring, piping and
additional information.
F.
Vent Damper Sequence of Operation.
See Figure 26
for schematic wiring diagram (16H-340 - 16H-505).
1. The Vent Damper is continuously powered at
Terminal 1.
2. When there is a call for heat, the damper relay coil
is energized through Terminal 5 if all limits ahead of
the damper are satisfied.
3. The relay coil closes contacts which energize the
damper motor, causing the damper to open.
4. When the damper blade reaches the fully open
position, power is sent back to the ignition circuit
through Terminal 2 and the damper motor is de-
energized.
5. When the call for heat is satisfied, the damper
relay coil is de-energized - closing contacts which
energize the damper motor. This causes the damper
to close. When the damper blade reaches the fully
closed position, the damper motor is de-energized.
POWER FAILURE - The damper blade will stop in the
position it was in when power failed. (Combustion
can never take place unless the damper blade is in
the fully open position).
G.
Sequence of Operation and Wiring.
Refer to Table
10 for the appropriate control system.
H.
Optional Low-Water Cut-Off Wiring.
See Figures 42
through 44.
Table 9: Heat Anticipator Settings
Control System
Heat Anticipator Setting*
Intermittent Circulation
24V Electronic Ignition
0.3
* If room is heated above thermostat temperature setting, reduce
heat anticipator setting by 0.1 or 0.2 amps. If boiler short cycles
without room reaching desired temperature, increase heat
anticipator by 0.1 or 0.2 amps.
Summary of Contents for 16H-340
Page 13: ...13 Figure 8 Jacket Assembly ...
Page 14: ...14 Figure 9 EP CSD 1 Control Installation ...
Page 16: ...16 Figure 11 Main Gas Piping Intermittent Ignition EI ...
Page 17: ...17 Figure 12 Schematic Pilot Piping Honeywell EI USA ...
Page 18: ...18 Figure 15 Schematic Gas Piping EP CSD 1 Control System 16H 410 16H 505 ...
Page 37: ...37 Figure 41 Operating Instructions EI ...
Page 47: ...47 Honeywell EI Trouble Shooting Guide ...
Page 48: ...48 THIS PAGE LEFT BLANK INTENTIONALLY ...
Page 58: ...58 ...
Page 60: ...60 ...