72
MYDENS
COSMOGAS
7 - USE
Error
Error description
Checks
Solutions
Err 164 Low water flow error (only for
2117
=
3
)
Check that the water flow rate
(par
1062
) is higher than par
2140
Check that the pump is working.
- Check that there are no obstructions that
prevent water circulation;
- Check that the heat exchanger is not
blocked;
Err 165 Electrical voltage too low
Check the electrical voltage
Err 166 Electrical voltage too high
Check the electrical voltage
Err 168 Flue gas maximum temperature.
WARNING!!! If the lock is repeated more
than once a day, switch-off the appliance
and contact a qualified service centre.
NOT ATTEMPT TO REPAIR THE
APPLIANCE.
Check that there is no air in the heating
circuit; perform any vents from the highest
radiators;
Vent the air from the appliance.
Check that the pump works correctly;
If the pump is not working, it must be
replaced.
Check that the flue gas temperature is
not more than 30°C above the return
temperature.
If the difference between the return
temperature and the flue gas temperature
is above 30°C, contact a qualified service
centre.
Measure the appliance efficiency, it must
correspond to value declared in the
technical features.
If the efficiency does not correspond to the
data at the end of the manual, the primary
heat exchanger is probably dirty from the
flue gas side or the water side. Clean and
check efficiency again.
No Conn Communication error on the display
Check correct connection to the display.
Restore the correct connection to the
display.
Check the correct connection to the
pressure sensor.
Restore the correct connection to the
pressure sensor.
Check correct connection to the water flow
sensor.
Restore the correct connection to the water
flow sensor.