59
MYDENS
COSMOGAS
7 - USE
Parameter
Description of the parameter
Access
level
U.M.
Range
Factory
value
Customised
values
2043
DHW/heating priority timing
Installer
mins
1...255
60
2044
DHW post-circulation
Installer
Sec
0...900
40
2045
Puffer PID factor P
Factory
#
0...1275
50
2046
Puffer PID factor I
Factory
#
0...1275
270
2047
Puffer PID factor D
Factory
#
0...1275
0
2048
Desired DHW temperature
Installer
°C
40...80
50
2049
Instant DHW negative hysteresis
Factory
°C
0...20
5
2050
Instant DHW positive hysteresis
Factory
°C
0...20
5
2051
Instant DHW PID factor P
Factory
#
0...1275
50
2052
Instant DHW PID factor I
Factory
#
0...1275
270
2053
Instant DHW PID factor D
Factory
#
0...1275
0
2060
DHW flow rate detection
Factory
l/min
0,1...20,0
2,5
2061
Flow rate at which the setpoint can be reached at
minimum power (N/A)
Factory
l/min
2,5
2062
Flow rate at which the setpoint can be reached at
maximum power (N/A)
Factory
l/min
2,5
2063
DHW modulation timing ON/OFF
Factory
Sec
30
2064
DHW recirculation pre-heat mode
Installer
#
0 = Off;
1 = Frost protection (N/A);
2 = Eco (recirculation kept at
value set under 2065);
3 = Comfort (recirculation keep at
DHW temperature);
0
2065
ECO recirculation temperature (See par. 2064)
Factory
°C
20...60
30
2067
Recirculation pre-heat timer after demand
Factory
Sec
0...255
30
2068
DHW timer after demand
Factory
Sec
0...255
120
2069
Recirculation pre-heat negative hysteresis
Factory
°C
0...30
0
2070
Recirculation pre-heat positive hysteresis
Factory
°C
0...30
5
2071
Recirculation pre-heat delay
Factory
Sec
0...15
10
2091
Maximum DHW temperature setting
Installer
°C
50...90
60
2092
Maximum fan speed setting
Factory
RPM 1750...9999
2093
Minimum fan speed setting
Factory
RPM 500...7050
2094
Setting fan speed ignition
Factory
RPM 1950...7050
2096
Minimum DHW temperature setting
Installer
°C
20...50
40
2109
Outdoor reset offset adjustment
(parameter 2001 = 1 or 2)
Installer
°C
OFF -10...10
0
2110
Minimum heating temperature setting for 0-10V
control (2001=4)
Installer
°C
20...50
20
2111
Maximum heating temperature setting for 0-10V
control (2001=4)
Installer
°C
50...90
80